6 Set up with the display and adjustment module
FIBERTRAC 31 • Profibus PA
43833-EN-170126
In menu item "
Scaling unit
" you define the scaling variable and the
scaling unit for the pulse rate on the display, e.g. volume in percent.
In menu item "
Scaling
" you define the scaling format on the display
and the scaling of the measured values for 0 % and 100 %.
Measured value min.
Measured value max.
To damp process-dependent measured value fluctuations, you can
set a time of 0 … 999 s in this menu item.
The default setting is a damping of 0 s.
In the menu item "
Lock/unlock adjustment
", you can protect the sen-
sor parameters against unauthorized or inadvertent modification. The
sensor is locked/unlocked permanently.
With locked instrument, only the following adjustment functions are
possible without entering a PIN:
•
Select menu items and show data
•
Read data from the sensor into the display and adjustment mod
-
ule.
Before you lock the sensor in unlocked condition, you can modify the
four-digit PIN number.
Keep the entered PIN number in mind. Operation of the sensor is only
possible with this PIN number.
Setup - AI FB1 - Scaling
unit
Setup - AI FB1 - Scaling
Setup - AI FB1 - Damping
Lock/unlock setup - Ad-
justment