SRC-C1T1 

CO2+T

EMPERATUR 

T

RANSMITTER

/M

ONITOR

 

 

Doc: 70-00-0794A, V2.7, 20210310 

© Vector Controls GmbH, Switzerland 

Page 7-10 

Subject to change without notice 

www.vectorcontrols.com 

Examples of temperature output signal on AO2: 

Output signal range = 

0…10 VDC 

(JP2 jumper setting) 

 

Default setting 

Custom setting 

IP 03 = -40 °C, IP 04 = 60 °C (range) 

IP 03 = -40 °C, IP 04 = 60 °C (range) 

OP 03 = 0 (temperature value) 

OP 04 = 0 % (limitation) 

OP 05 = 100 % (limitation) 

OP 03 = 0 (temperature value) 

OP 04 = 20 % (limitation) 

OP 05 = 80 % (limitation) 

100%

10 V

0%

0 V

-40

60

°C

Output

-40

60

°C

Output

20%

2 V

80%

8 V

 

Error messages shown on OPA-S 

Error 

Description 

Err 1: 

Communication error: Verify cable connections, cable type and maximum distance. 

Err 2: 

Temperature sensor error (element damaged or missing) 

Err 3: 

CO2 sensor error: Make sure the sensor is not miss-calibrated. If possible, execute 400 ppm calibration. (see 

section 

Calibration

 on page 

8). 

If error cannot be removed by calibrating the sensor, replace product. 

 

Use the CO2-Transmitter as P-Controller 

The CO2-transmitter may be converted into a proportional fresh air controller through a simple change of two parameter 

settings: 

1.

 

Set a minimum concentration when the fresh air fan should start to run at its minimum speed for example 500 

ppm. Set this as the minimum value in the 

IP 08 

parameter. 

2.

 

Then define the value when the fan should run at full speed, for example 1000 ppm and set this value in

 IP 09

. 

Your transmitter has now been converted into a P-Controller! 
By using the analog output, the fan will start to run if the CO2 concentration is higher than 500 ppm. It increases to its 

maximum when CO2 concentration reaches 1000 ppm. 

 

Status-LED 

 

 

 

 

 

Status LED 

- No light 

: No power or unit damaged 

- 5 sec flashing 

: Normal 

- 2 second blinking 

: Calibration 

- 10 second pulse 

: Calibration successful 

- Constant red > 10 sec 

: Calibration or sensor error 

 

Red Status-LED

 

Summary of Contents for 40-300198

Page 1: ...ers and if required by a programming module Standard signal ranges are 0 10 VDC and 2 10 VDC Other ranges can be defined by using the external display and programming module OPA S For OPA S usage see section Parameter configuration on page 5 Automatic baseline calibration ABC The ABC background calibration constantly supervises the measured CO2 concentrations The calibration function expects the C...

Page 2: ...ort applications It is not a safety device Where a device failure could endanger human life and property it is the responsibility of the client installer and system designer to add additional safety devices to prevent such a device failure Ignoring specifications and local regulations may cause equipment damage and endangers life and property Tampering with the device and misapplication will void ...

Page 3: ...pensation to stabilize after power up Signal outputs Analog outputs Output signal Resolution Maximum load DC 0 10 V or DC 2 10 V 10 bit 9 7 mV Voltage signal 1kΩ Relays output Insulation strength between relays and system electronics between neighboring contacts 48 VAC 1 A max 30 VDC 1 A max 500 VAC to EN 60 730 1 500 VAC to EN 60 730 1 Environment Operation Climatic conditions Temperature Humidit...

Page 4: ...ct exposure to sunlight o Do not install near heat sources e g radiators or other heat generating devices o Areas with poor air circulation and niches e g behind doors or shelves o Outside walls insufficiently insulated o In the direct influence area of ventilation openings and fans Mounting instruction See SRC C1T1 installation sheet no 70 000809 www vectorcontrols com Dimension mm inch 1 2 3 4 C...

Page 5: ...cified with output parameter OP 01 and OP 02 is left at the default value of 0 100 With any other setting the position of JP2 has no influence and the signal range defined with the output parameters applies For jumper location see section Wiring and Connection on page 4 Parameter configuration The transmitter can be adapted to fit perfectly into any application by adjusting the software parameters...

Page 6: ... calibration default 1 Calibrate to gas 0 ppm 2 Calibrate to fresh air 400 ppm 0 2 0 1 Sample interval 1 sec 2 Changing this parameter affects the control of the air quality LEDs or relay as follows Air quality LED Use of Parameters Green IP 08 value IP 10 value 400 2 Green Orange IP 10 value 400 2 IP 10 value Orange IP 10 value IP 10 value IP 11 value 2 Orange Red IP 10 value IP 11 value 2 IP 11 ...

Page 7: ...xecute 400 ppm calibration see section Calibration on page 8 If error cannot be removed by calibrating the sensor replace product Use the CO2 Transmitter as P Controller The CO2 transmitter may be converted into a proportional fresh air controller through a simple change of two parameter settings 1 Set a minimum concentration when the fresh air fan should start to run at its minimum speed for exam...

Page 8: ...tion Once the calibration has been executed the status LED will show constant RED and the green air quality led will blink for 10s if successful If calibration is not successful no stability of concentration for 5 min no communication with sensor the red air quality led will blink instead and the status LED will stay constantly on red in error mode Recalibrate or restart device to stop error mode ...

Page 9: ...SRC C1T1 CO2 TEMPERATUR TRANSMITTER MONITOR Doc 70 00 0794A V2 7 20210310 Vector Controls GmbH Switzerland Page 9 10 Subject to change without notice www vectorcontrols com Blank page ...

Page 10: ...V2 7 20210310 Vector Controls GmbH Switzerland Page 10 10 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorcontrols com www vectorcontrols com ...

Reviews: