background image

 

SRC-C1T1 

CO2+T

EMPERATUR 

T

RANSMITTER

/M

ONITOR

 

 

Doc: 70-00-0794A, V2.7, 20210310 

© Vector Controls GmbH, Switzerland 

Page 2-10 

Subject to change without notice 

www.vectorcontrols.com 

Minimum and maximum values 

Using a display & programming module OPA-S, the user has the option to read out and reset the CO2 and temperature 

minimum and maximum values. The minimum and maximum values may as well be used as output signals. The minimum 

and maximum values are automatically saved to the device and are available after a power interruption. 

 

For OPA-

S usage see section 

Displaying minimum and maximum values

 on page 

5. 

Indication of air quality (CO2 concentration) 

Three color LEDs are used to indicate air quality: Green for low CO2 concentration, orange for medium and red for high 

concentration. The levels for low-medium-high may be programmed. 
 

 

Safety 

 

DANGER! Safety advice 

This device is for use as a CO2 concentration indicator and a CO2 and temperature transmitter for comfort 

applications. It is not a safety device. Where a device failure could endanger human life and property, it is the 

responsibility of the client, installer and system designer to add additional safety devices to prevent such a device 

failure. Ignoring specifications and local regulations may cause equipment damage and endangers life and 

property. Tampering with the device and misapplication will void warranty. 

 

Ordering information 

Product Name 

Product Nr. 

Description/Option 

CO2+Temperature Sensor

 

SRC-C1T1 

40-300198 

CO2+temperature transmitter / monitor 

Accessories

 

OPA-S 

40-500006 

External display and programming module. 

Note: For the correct display of values, V1.7 and later is required. 

 

 

 

Red-LED 

Orange-LED

 

Green-LED

 

Air quality LED 

No light 

: No power or unit damaged 

Green 

: High air quality (low CO2 level) 

Green + Orange  : Good air quality 
Orange 

: Moderate air quality (medium CO2 level) 

 Red 

: Low air quality 

Red 

: Poor air quality (high CO2 level) 

Red blinking 

: 0 ppm calibration 

Green blinking 

: 400 ppm calibration 

 

Default CO2 indication setting 

Air quality LED 

CO2 range in ppm 

Green 

0…

699 

Green + Orange 

700

999 

Orange 

1000

…1

299 

 Red 

1300…1599

 

Red 

1600…2000

 

 

Summary of Contents for 40-300198

Page 1: ...ers and if required by a programming module Standard signal ranges are 0 10 VDC and 2 10 VDC Other ranges can be defined by using the external display and programming module OPA S For OPA S usage see section Parameter configuration on page 5 Automatic baseline calibration ABC The ABC background calibration constantly supervises the measured CO2 concentrations The calibration function expects the C...

Page 2: ...ort applications It is not a safety device Where a device failure could endanger human life and property it is the responsibility of the client installer and system designer to add additional safety devices to prevent such a device failure Ignoring specifications and local regulations may cause equipment damage and endangers life and property Tampering with the device and misapplication will void ...

Page 3: ...pensation to stabilize after power up Signal outputs Analog outputs Output signal Resolution Maximum load DC 0 10 V or DC 2 10 V 10 bit 9 7 mV Voltage signal 1kΩ Relays output Insulation strength between relays and system electronics between neighboring contacts 48 VAC 1 A max 30 VDC 1 A max 500 VAC to EN 60 730 1 500 VAC to EN 60 730 1 Environment Operation Climatic conditions Temperature Humidit...

Page 4: ...ct exposure to sunlight o Do not install near heat sources e g radiators or other heat generating devices o Areas with poor air circulation and niches e g behind doors or shelves o Outside walls insufficiently insulated o In the direct influence area of ventilation openings and fans Mounting instruction See SRC C1T1 installation sheet no 70 000809 www vectorcontrols com Dimension mm inch 1 2 3 4 C...

Page 5: ...cified with output parameter OP 01 and OP 02 is left at the default value of 0 100 With any other setting the position of JP2 has no influence and the signal range defined with the output parameters applies For jumper location see section Wiring and Connection on page 4 Parameter configuration The transmitter can be adapted to fit perfectly into any application by adjusting the software parameters...

Page 6: ... calibration default 1 Calibrate to gas 0 ppm 2 Calibrate to fresh air 400 ppm 0 2 0 1 Sample interval 1 sec 2 Changing this parameter affects the control of the air quality LEDs or relay as follows Air quality LED Use of Parameters Green IP 08 value IP 10 value 400 2 Green Orange IP 10 value 400 2 IP 10 value Orange IP 10 value IP 10 value IP 11 value 2 Orange Red IP 10 value IP 11 value 2 IP 11 ...

Page 7: ...xecute 400 ppm calibration see section Calibration on page 8 If error cannot be removed by calibrating the sensor replace product Use the CO2 Transmitter as P Controller The CO2 transmitter may be converted into a proportional fresh air controller through a simple change of two parameter settings 1 Set a minimum concentration when the fresh air fan should start to run at its minimum speed for exam...

Page 8: ...tion Once the calibration has been executed the status LED will show constant RED and the green air quality led will blink for 10s if successful If calibration is not successful no stability of concentration for 5 min no communication with sensor the red air quality led will blink instead and the status LED will stay constantly on red in error mode Recalibrate or restart device to stop error mode ...

Page 9: ...SRC C1T1 CO2 TEMPERATUR TRANSMITTER MONITOR Doc 70 00 0794A V2 7 20210310 Vector Controls GmbH Switzerland Page 9 10 Subject to change without notice www vectorcontrols com Blank page ...

Page 10: ...V2 7 20210310 Vector Controls GmbH Switzerland Page 10 10 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorcontrols com www vectorcontrols com ...