TLC3-ECO Economizer 

C

ONTROL 

C

ONFIGURATION

 

 

Doc: 70-00-0660, V1.1, Date: 20170322 

© Vector Controls GmbH, Switzerland 

Page 8 

Subject to alteration 

Control configuration (password 241) 

Warning! Only experts should change these settings! 

Setpoint limits 

Parameter  Description 

Range 

Default 

CP 00 

Minimum set point limit in heating mode 

-40-60°C 

16°C (61°F) 

CP 01 

Maximum set point limit in heating mode 

-40-60°C 

30°C (87°F) 

CP 02 

Minimum set point limit in cooling mode 

-40-60°C 

16°C (61°F) 

CP 03 

Maximum set point limit in cooling mode 

-40-60°C 

30°C (87°F) 

Controls configuration 

CP 04 

Economy (unoccupied) mode temperature shift: 
The comfort (occupied) setpoint is shifted by the value set with 

parameter. If heating is active the comfort setpoint will be 

decreased, if cooling is active, the setpoint will be increased. 
(Enable with UP06.) 

0-10.0°C 

5°C (10°F) 

CP 05 

Dead zone span: 
The dead zone span lies between the heating and the cooling 

setpoint. The output is off while the temperature is within the dead 

zone span. A negative dead zone is not possible. 

0-100°C 

1.0°C (2°F) 

CP 06 

Heat/Cool changeover delay (if set to CP12 = 3): 
A demand to switch between heating and cooling must persist for 

the length of time set with this parameter before the controller 

switches. Prevents activation of a sequence during a short-term 

change in temperature in order to protect equipment (with control 

overshoot for example). 

0…255 min 

5 min 

CP 07 

Min. temperature difference required to start free heating 

0-10.0°C 

1.0°C (2.0°F) 

CP 08 

Min. temperature difference required to start free cooling 

0-10.0°C 

1.0°C (2.0°F) 

CP 09 

Switching hysteresis  
is the difference between switching on and switching off. A small 

hysteresis will increase the number of switching cycles and thus 

the wear on associated equipment. 

0-10.0°C 

0.5°C (1°F) 

CP 10 

Delay OFF (minimum running time),  
The minimum time the damper is open 

0…255 s 

200s 

CP 11 

Delay ON (minimum stopping time) 
The minimum time the damper is closed.   

0…255 s 

200s 

CP 12 

Control option:  
0 = Cooling only 

1 = Heating only 

2 = Manual heat – cool switching 

3 = Demand based heat – cool switching 

0…3 

Default = 3 

W01 = 0 

W02 = 1 

W03 = 2 

W04 = 3 

 

Control logicfree cooling 

If the room temperature is above the setpoint, the controller will open the outside damper if the outdoor 

temperature is below the room temperature with a minimum difference as specified under CP08.  

Once the outdoor damper is open, it will stay open until the setpoint is reached or outdoor temperature is higher 

than room temperature.  

If the outdoor damper closed because the setpoint is reached, it will re-open after the indoor temperature 

increased for the amount specified under hysteresis CP09. 

 

 

Control logicfree heating 

If the room temperature is below the setpoint, the controller will open the outside damper if the outdoor 

temperature is above the room temperature with a minimum difference as specified under CP07.  

Once the outdoor damper is open, it will stay open until the setpoint is reached or outdoor temperature is lower 

than room temperature.  

If the outdoor damper closed because the setpoint is reached, it will re-open after the indoor temperature 

decreased for the amount specified under hysteresis CP09. 

Summary of Contents for 40-10 0214

Page 1: ...e input heat cool changeover or high low limit The economizer controls an outdoor damper and optional fan It activates the outdoor damper if there is heating or cooling demand and if outdoor condition...

Page 2: ...tic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conformity RoHS directive...

Page 3: ...diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the mounting screw heads do not stand out more...

Page 4: ...ue Small digits show set point Vertical bars show analog output value Arrows in position 1 2 and or 3 show active binary digital output stages Power failure All parameters and set points are memorized...

Page 5: ...4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set ON or O...

Page 6: ...inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to s...

Page 7: ...ture sensor X1 10 to 10 in 0 1 steps 10 10 0 UP 10 Calibrate external temperature sensor X2 10 to 10 in 0 1 steps 10 10 0 UP 11 Select contents of Large LCD display in standard mode 0 6 2 Indoor Tempe...

Page 8: ...F CP 08 Min temperature difference required to start free cooling 0 10 0 C 1 0 C 2 0 F CP 09 Switching hysteresis is the difference between switching on and switching off A small hysteresis will incre...

Page 9: ...tion Function of mechanical heating or cooling activation If there is heating or cooling demand The controller verifies if free heating or cooling is possible based on control logic mentioned on the l...

Reviews: