background image

 

TLC3-ECO Economizer 

O

PERATION

 

 

Doc: 70-00-0660, V1.1, Date: 20170322 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alteration 

Technical specifications 

Notice!

 Failure to follow specifications and local regulations may cause equipment damage. Misapplication will void 

warranty. 

Power supply 

Power requirements  

210 

– 250 V AC 50/60 Hz 

Power consumption 

Max 1W, 1.5VA 

Electrical connection 

Terminal connectors 

Clock backup 

Min 48h if charged for 24h 

Signal inputs 

Temperature inputs 

Range 
Accuracy 

RT internal 
0…50 °C (32…122 °F) 
0.5°C (1°F) 

 

 

Input type: 
Range 
Accuracy 

External (Sxx-Tn10 sensor) 
-40..70°C (-

40…158°F) 

0.5°C (1°F) if 0...50°C (32....122°F) 
1.0°C (2°F) if -40...70°C (-40...158°F) 

Signal outputs 

Digital switching outputs 

Switching type 
AC switching power 

Insulation strength 

between relays contacts and system electronics: 
between open relays contacts 

Y1 to Y2 
Relays 
0…250V AC 1.25A max. each output 
 
4000VAC 
1000VAC 

Environment 

Operation 
Climatic conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0…50 °C (32…122 °F) 
<95 % r.H. non-condensing 

 

Transport & storage 
Climatic conditions 
Temperature 
Humidity 
Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25

…70 °C (-13…158 °F) 

<95 % r.H. non-condensing 
class 2M2 

Standards 

conformity 
RoHS directive 
EMC directive 
Low voltage directive 

2011/65/EU 
2004/108/EC 
2006/95/EC 

 

Product standards 

Automatic electrical controls for household and similar use 
Special requirement on temperature dependent controls 

 
EN 60 730 

–1:2011 

EN 60 730 

– 2 – 9:2010 

 

Electromagnetic compatibility for  
domestic sector 

Emissions: EN 60 730-1:2011 
Immunity: EN 60 730-1:2011 

 

Degree of protection 

IP30 to EN 60 529 

 

Pollution class 

II (EN 60 730-1:2011) 

 

Safety class 

II (IEC61140:2001+ A1:2004) 

 

Overvoltage category 

III (EN 60 730-1:2011) 

 

Restriction of the use of certain hazardous substances 

EN 50581:2012 

General 

Dimensions (H x W x D) 

Front: 
Power case: 

21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)  
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) 

 

Material:  

Cover, back part 
Mounting plate 

ABS plastic (UL94 class V-0) 
Galvanized steel 

 

Weight (including package) 

Standard:  

295g (10.4oz) 

Deluxe (-D):  

305g (10.7oz) 

Dimensions, mm (inch) 

 

 

88 (3.5) 

32 (1.2) 

8

8

 (

3

.5

21  

(0.8) 

Space required in flush mounting box: 
(H x W x D)  
60 x 50 x 32 mm (2.4 x 2.0 x 1.26 in.) 
 
Distance for mounting screws: 
Horizontal and vertical:  
45 to 63 mm (1.8 to 2.5 in.) 
 

Summary of Contents for 40-10 0214

Page 1: ...e input heat cool changeover or high low limit The economizer controls an outdoor damper and optional fan It activates the outdoor damper if there is heating or cooling demand and if outdoor condition...

Page 2: ...tic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conformity RoHS directive...

Page 3: ...diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the mounting screw heads do not stand out more...

Page 4: ...ue Small digits show set point Vertical bars show analog output value Arrows in position 1 2 and or 3 show active binary digital output stages Power failure All parameters and set points are memorized...

Page 5: ...4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set ON or O...

Page 6: ...inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to s...

Page 7: ...ture sensor X1 10 to 10 in 0 1 steps 10 10 0 UP 10 Calibrate external temperature sensor X2 10 to 10 in 0 1 steps 10 10 0 UP 11 Select contents of Large LCD display in standard mode 0 6 2 Indoor Tempe...

Page 8: ...F CP 08 Min temperature difference required to start free cooling 0 10 0 C 1 0 C 2 0 F CP 09 Switching hysteresis is the difference between switching on and switching off A small hysteresis will incre...

Page 9: ...tion Function of mechanical heating or cooling activation If there is heating or cooling demand The controller verifies if free heating or cooling is possible based on control logic mentioned on the l...

Reviews: