TLC3-ECO Economizer 

O

PERATION

 

 

Doc: 70-00-0660, V1.1, Date: 20170322 

© Vector Controls GmbH, Switzerland 

Page 5 

Subject to alteration 

Manual heat – cool change 

To manually change heating or cooling mode press the OPTION key for more than 2 seconds.  

Access to manual heat – cool change may be disabled with parameter UP03. 

For TLC3-ECO:  

Press OPTION > 2 sec. SEL and H-C is displayed.  

For TLC3-ECO-D:   Press OPTION > 2 sec. SEL and current time is displayed.  
 

Press UP key twice. SEL and H-C is displayed. 

 

Press OPTION again to toggle H or C.  

SEL 
  H-C 

 

Clock operation  

TLC3-ECO-Dcontains a quartz clock with battery back-up (not available in TLC3-ECO). Up to 8 mode changes based on 

time and day of the week may be programmed. Also position an output or select a set point directly with a time 

schedule. A blinking clock indicates that the time has not been setor thatthe unit has beenwithout power for longer 

than 48 hours. The time needs to be set to allow time schedules to operate. 

 

Clock setup 

Press OPTION > 2 sec. SEL and current time displayed 
Press OPTION< 2 sec. to change time, 

Minutes blink: UP/DOWN to change, OPTION to save minutes, 
Hours blink: UP/DOWN to change, OPTION to save hour, 

Press OPTION to save time, 

DAY1 blinks: UP/DOWN to change, OPTION to save day 

SEL 
  00:00 
  DAY1 (Mon) 

 

Creating time schedules 

There are a total of 4 switching events grouped into 4 time schedule group. A switching event consists of an operation 

mode and a switching time.  

Step 1: Select time schedule group 

Press OPTION > 2 sec. SEL and current time displayed 

Press UP:  

SEL and PRO displayed, clock symbol blinks 

Press OPTION:  

Select time schedule program. Pro 1 to Pro 4. PRO 1 is shown. 1 is blinking. 
UP/DOWN to change, OPTION to select 

SEL 
  PRO 

 

Pro 1 to Pro 4 
  OFF/ON 

 

Step 2: Enable/disable time schedule group 

Pro x is fixed now, ON / OFF blinks 

Press UP/DOWN to set ON or OFF. This disables or enables the time schedule group. Press OPTION to 
continue 

In case OFF has been selected, return to Step 1. If ON is selected, continue to step 3.  

Pro 1 
  OFF/ON 

 

Step 3: Selected switching day (Pr01) to DAY1 (Mon) – DAY 7 (Sun) for time schedule group 

While Pro1 is displayed and day selection is blinking: 
Press UP / DOWN:   

select day group: d1-7, d1-5, 1-6, d6-7, day 1, day 2, day 3, day 4, day 5, day 6, day 7 
d1-7 will activate the time schedule group for all 7 week days, d1-5 activates it only for day 1 (Mon) 
to day 5 (Fri) etc.  

Press OPTION to save day selection and move to first switching event.  

Pr01 
DAY1 

 

 

Step 4: Select action for switching event 

The bar on the right side indicates the current number of the switching event.  

There are a total of 4 switching events per group.  
 
Press UP / DOWN 

to select desired operation mode. (no, OFF, ECO, ON, UNI),  

 

no = disables this switching time 

 

OFF = switches unit Off, enables reset timer 

 

ECO = sets operation mode to On and Economy, disables reset timer 

 

ON = sets operation mode to On and Comfort, disables reset timer 

 

UNI = Does not change operation mode, only disables reset timer 

Press OPTION to continue 

Pr01 
    no 

 
 

Step 5: Select a switching time for switching event 

Press UP / DOWN 

 

Switching time 07:30 blinks. Select switching time in 15 min steps from 00:00–23:45.  

Press OPTION to save switching time: 
 

 

Pr01 
  08:00

 

Step 6: Complete time schedule group definition 

Repeat steps 4 and 5 for all 4 switching events. In case a switching event is not used, set its mode to “no”.  
 
To review the entire schedule group, step through by repeatedly pressing the OPTION key from step 1 onwards 
to step 6.  
 

Pr01 
   08:00

 

 

Summary of Contents for 40-10 0214

Page 1: ...e input heat cool changeover or high low limit The economizer controls an outdoor damper and optional fan It activates the outdoor damper if there is heating or cooling demand and if outdoor condition...

Page 2: ...tic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conformity RoHS directive...

Page 3: ...diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the mounting screw heads do not stand out more...

Page 4: ...ue Small digits show set point Vertical bars show analog output value Arrows in position 1 2 and or 3 show active binary digital output stages Power failure All parameters and set points are memorized...

Page 5: ...4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set ON or O...

Page 6: ...inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to s...

Page 7: ...ture sensor X1 10 to 10 in 0 1 steps 10 10 0 UP 10 Calibrate external temperature sensor X2 10 to 10 in 0 1 steps 10 10 0 UP 11 Select contents of Large LCD display in standard mode 0 6 2 Indoor Tempe...

Page 8: ...F CP 08 Min temperature difference required to start free cooling 0 10 0 C 1 0 C 2 0 F CP 09 Switching hysteresis is the difference between switching on and switching off A small hysteresis will incre...

Page 9: ...tion Function of mechanical heating or cooling activation If there is heating or cooling demand The controller verifies if free heating or cooling is possible based on control logic mentioned on the l...