TLC3-ECO Economizer 

O

PERATION

 

 

Doc: 70-00-0660, V1.1, Date: 20170322 

© Vector Controls GmbH, Switzerland 

Page 4 

Subject to alteration 

Display and operation 

 

Operation mode 

 

Comfort (occupied) 

All control functions operating per set points. 

 

Economy (unoccupied): 

Set points shifted according to 

Parameters CP04.

 

Economy mode and setpoint shift may be disabled with UP06 

OFF 

Energy Hold Off 

Outputs are off 

 

Heating 

Output activates if control temperature lower than setpoint.  

While blinking, free heating is active. Outside temperature is higher than inside 

temperature. 

 

Cooling 

Output activates if control temperature higher than setpoint.  

While blinking, free cooling is active. Outside temperature is lower than inside 

temperature.  

 

Manual mode 

Deluxe only: Override of time schedule active.  

 

Schedule 

Deluxe only: Time schedule is active 

 

Fan 

If present: Fan is running 

 

External limit switch 

External limit switch is off, output is deactivated 

Standard display (parameters UP10, UP11) 

 

Active whenno key has been pressed for 30 seconds. 

 

Contents may be chosen with parameters.  

Loop display 

 

Active when changing set points. Large digits show input value. Small digits show set point. Vertical bars show 

analog output value. Arrows in position 1, 2 and/or 3 show active binary (digital) output stages 

Power failure 

 

All parameters and set points are memorized and do not need to be re-entered.  

 

Upon return of power: Set

Parameter UP05

to keep the unit off, switch on, or operation mode before power failure. 

 

Clock and time schedule settings retained for 48 hours (after powered for at least 10 hours). 

Error messages 

Err1:

 

Error temperature sensor. The temperature sensor may be damaged or not present 

 

 

Left (POWER):  

Press < 2 sec.: Toggle Economy - 
Comfort mode or switch from OFF 
to ON 
Press > 2 sec.: Turn unit OFF. Text 
OFF displayed with current time 
(deluxe) temperature (standard) 
(Parameter setting: Return to 
previous level. ESC) 
 

Up : 

Increase setpoint  
(Parameter setting: 
scroll menu options 
and parameters) 
 

Down:  

Decrease setpoint  
(Parameter setting: scroll menu 
options and parameters) 
 

Mode 

Display of operation 

mode 

 
 

Large digits 

Display of input or parameter value 

Indicators left 

1.  Y1 
2.   Y2 

Vertical bar 

(Active stage or proportional output 
in 10% steps) 

Small digits 

Display of setpoint, clock or 
parameter number. 

Right (OPTION)  

Press < 2 sec.: Select setpoint 
Press > 2 sec.: Manual H/C change 
(Parameter setting: ENTER to 
select menu option, accept 
parameter change) 

Indicator right 

Outdoor temperature exceeds limit 

Summary of Contents for 40-10 0214

Page 1: ...e input heat cool changeover or high low limit The economizer controls an outdoor damper and optional fan It activates the outdoor damper if there is heating or cooling demand and if outdoor condition...

Page 2: ...tic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conformity RoHS directive...

Page 3: ...diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the mounting screw heads do not stand out more...

Page 4: ...ue Small digits show set point Vertical bars show analog output value Arrows in position 1 2 and or 3 show active binary digital output stages Power failure All parameters and set points are memorized...

Page 5: ...4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set ON or O...

Page 6: ...inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to s...

Page 7: ...ture sensor X1 10 to 10 in 0 1 steps 10 10 0 UP 10 Calibrate external temperature sensor X2 10 to 10 in 0 1 steps 10 10 0 UP 11 Select contents of Large LCD display in standard mode 0 6 2 Indoor Tempe...

Page 8: ...F CP 08 Min temperature difference required to start free cooling 0 10 0 C 1 0 C 2 0 F CP 09 Switching hysteresis is the difference between switching on and switching off A small hysteresis will incre...

Page 9: ...tion Function of mechanical heating or cooling activation If there is heating or cooling demand The controller verifies if free heating or cooling is possible based on control logic mentioned on the l...

Reviews: