6.10. Menu point 10 – Level of fixed frequency right
(Range from 0 to Fmax in Hz)
Adjusted level of the fixed frequency which should be fixed as set point.
The range is between 0 and the maximum output frequency (maximum of 99Hz).
6.11. Menu point 11 – Level of fixed frequency left (ccw)
(Range from 0 to Fmax in Hz)
See menu point 10.
6.12. Menu point 12 – Factory settings
The activation of the factory setting causes the overwriting of all parameters with factory preset values:
Running up ramp right(cw)
: 50 Hz
Running down ramp right/cw
: 50 Hz
Running up ramp left/ccw
: 50 Hz/s
Running down ramp left/ccw
: 50 Hz/s
Boost
: 5 %
Setpoint
: Pushbutton with setpoint saving
Display setting
: Set point
Max. Output frequency
: 50 Hz
Corner frequency
: 50 Hz
Fixed frequency right/cw
: 0 Hz
Fixed frequency left/ccw
: 0 Hz
Output relay
: Collective fault message
Final value frequency
: 0 Hz/s
Over current value
: 2,0 A
Power ON/OFF – Button
: Activated
Min.Output frequency at analogue
: 5 Hz
Display illustration
: Normal
Parameter menu
: Not password protected