Bild 6.5.1 Output voltage as a function of frequency and boost
6.6. Menu point 06 – Setpoint
The VECTOR offers four basic options for setpoint, which can be set in this menu point. The set point
input via the buttons located on the device "Up" and "Down" is standard preset in the factory settings
and can be saved with 00 in menu point 06. Under 01 the setpoint input via the analog input is
activated. Here, for example, a potentiometer may be connected. By saving a 02 you reach a target
value via a pre-fixed frequency. This fixed frequency can be changed under Menu point 10 + 11.
6.7. Menu point 07 – Display representation
Under this menu item the nominal value can be displayed with 00 or the actual value with 01 in
operation.
6.8. Menu point 08 – Maximum field frequency
(Range from1 to 99 in Hz)
Previously adjusted maximum field frequency, which the inverter should not exceed, even at maximum
set point.
6.9. Menu point 09 – Nominal motor frequency
(Range from 30 to 99 in Hz)
Enter the rated frequency of the connected motor in Hz (corner frequency).