User Manual Frequency Inverter Vector Basic
MSF – Vathauer Antriebstechnik GmbH & Co KG
Tel: +49 (0) 5231 – 63030
Am Hessentuch 6-8
Fax: +49 (0) 5231-66856
32758 Detmold
Email:
Web: www.msf-technik.de
17 / 25
6.13. Menu point 13 – Output relay
This menu point allows conditions to choose when to switch the output relays:
00 = Collective fault message
01 = Set point value is actual value
02 = Actual value equal frequency (Frequency selectable in Menu 14)
03 = Over temperature internal
04 = Rotating field frequency unequal zero (Motor rotates)
05 = Motor over temperature (PTC)
06 = Fault IGBT module
07 = Short circuit motor
08 = Motor over current
09 = DC link overvoltage
10 = Set over current
11 = Frequency inverter ready for operation
6.14. Menu point 14 – Final value frequency
(Range from 0 to Fmax in Hz)
Under the menu point Output relay (menu point 13) it is possible under condition 02, to switch the
output relay when a certain frequency output is reached. This frequency can be adjusted in this menu.
6.15. Menu point 15 – Over current
(Range from 0,4 to 2,5A in 0,1A steps)
This menu point allows you to switch off the motor during a permanent over current. This means the
value on the 7-segment display shows the current in A (example: xx => x, x A). If the current is
continuously (approx. 75 sec) greater than the set value, then it is switched off. This shutdown can
only work reliable for motors between 0.12 kW and 0.37 kW. The setting 26 (equivalent to 2.6 A)
disables the over current shutdown
6.16. Menu point 16 – Adjustment for analog set point
This menu point provides for an adjustment for the analog set point. If required, e.g. an external
potentiometer to set to the maximum value and select menu item point 16 and hold down buttons Up /
Down together until the display flashes briefly.