18
Värmebaronen Viking Bio 35
Operation and maintenance
Resetting the thermal relay
When the thermal relay has been triggered, the ‘ALARM’
indicator lights up constantly.
Investigate and remedy the cause of the increased
temperature.
The burner must be disconnected from the power supply
when the thermal relay is reset.
Remove the cover of the burner and detach the cover plate
in front of the thermal relay.
Reset it by pressing the button on the thermal relay.
Refit the enclosure and restart the burner.
Reset button
Changing ignition element
Unscrew the screws that
hold the ignition unit
Ignition element
Outer pipe
Turn the outer pipe half
a turn and remove it.
Pull out the broken
ignition element and
replace it with a new
one.
Refit in reverse order.
Safety system
The pellet system’s safety system consists of:
• overheating protection against excessive boiler temperature.
• thermal relay.
• non-combustible hose (melts) between feed auger and
downpipe.
• fan with fan guard.
• photoresistor for flame monitoring.
• blockage if the ambient temperature is too high.
The majority of the functions cannot be influenced by the user
and require no special control.
Check regularly that the hose between the feed auger and
the downpipe is intact.
Changing the inner burner pipe
Detach the burner from the outer burner pipe.
Unscrew this screw. Turn the inner burner pipe anticlockwise
and pull the pipe out.
Move the lip suspended in the pipe to the new burner pipe.
Refit in reverse order.
Check the condition of the outer burner pipe as well.
Check that the burner has been disconnected
from the power supply before working on it!
Any intervention in the boiler’s electrical
equipment that requires tools must be carried out
under the supervision of a qualified electrician.
Disconnect the plug before service or if the
burner is removed from the boiler.