Värmebaronen EP- 900, -1080, -1200, -1400
Adjustment menu - with outdoor temperature compensation, OTC
Adjustment menu - boiler with UTC - Window one
ĮMAX SET LIMIT 95°C
MIN SET LIMIT 20°C
--------------------
RESET PEAK VAL. [OK]
ECO OUT TEMP 17°C
SHUT DOWN BOILER N
- - ï ï ï ï ï ï - -
ĮMAX SET LIMIT 95°C
ĮMIN SET LIMIT 20°C
Maximum and minimum temperature setpoint.
MAX SET LIMIT
55 - 105°C.
MIN SET LIMIT
20 - 50°C.
ĮRESET PEAK VAL. [OK]
Resetting the values in the information menu.
ĮECO OUT TEMP +17°C
Lowest temperature at which no heating is required. All boiler
power disconnected, the circulation pump is stopped.
Alternative
ĮCP FUNCTION ECO
in the Installa-
tion menu must be selected for the ECO function to be active
and for temperature setting to be carried out
ĮSHUT DOWN BOILER N
Set boiler in standby position (switched off).
Window two
Setpoint at outdoor temperature.
- - î î î î î î - -
Į P1, Tout= 20: 20°C
P2, Tout= 15: 27°C
P3, Tout= 10: 33°C
P4, Tout= 5: 40°C
P5, Tout= 0: 45°C
P6, Tout= -5: 49°C
- - ï ï ï ï ï ï - -
20°C
→
15°C
→
10°C
→
5°C
→
0°C
→
-5°C
→
Window three
Setpoint at outdoor temperature.
- - î î î î î î - -
Į P7, Tout=-10: 53°C
P8, Tout=-15: 57°C
P9, Tout=-20: 60°C
P10, Tout=-25: 62°C
P11, Tout=-30: 63°C
TEMP.ADJUST : 0°C
- MENU SELECTOR
-10°C
→
-15°C
→
-20°C
→
-25°C
→
-30°C
→
ĮTEMP.ADJUST 0°C
Alternative temperature, against normal temperature, +/-
adjustment of setpoint, parallel displacement.
The change is affected by a contact function connected to
terminal block J2, see point 32 “Control circuit”
Heating curve
P1
P2
P3
P4
P5
P6
P7
P8
P9 P10 P11
+20 +15 +10 +5
0
-5 -10 -15 -20 -25 -30
70
60
50
40
30
20
80
Framledningstemperatur
Utomhustemperatur
Flo
w
te
m
pe
ra
tu
re
Outdoor temperature
Each setpoint, P1 - P11, is adjustable over the range 20 - 80°C