34
Värmebaronen EP- 900, -1080, -1200, -1400
Technical Data
The electric boiler is manufactured in accordance with
Directive 2014/68/EU, Article 4.3.
The electric boiler can be supplied with factory-fitted
safety equipment, reviewed by accredited body accord-
ing to EN 12828.
Factory-fitted safety equipment includes:
2 x safety valves.
2 x high pressure guards.
1 x low pressure guard.
1 x automatic vent valve.
With factory-fitted safety equipment, the boiler can be
installed without expansion trap according to EN 12828.
Double circulation pumps and flow guards are not re-
quired. The boiler can cope with zero flow from a safety
perspective.
A steam-collecting vessel is not required. The safety
valves are fitted directly on the boiler's safety pipe.
Final examination, under national laws, that the elec-
tric boiler has the necessary safety equipment shall be
carried out by an accredited body when assessing the
monitoring interval for the electric boiler.