Parameter
Default
Description
1
2
3
4
5
Compensat. set 2
p = XX.X [bar]
0
Compensation at maximum frequency. By pressing the
green button it is possible to invert the sign.
x
Value set update
t = XX [s]
5
Time interval for updating the set value as a function of
compensation.
x
x
Operating freq.
f = XXX [Hz]
=
Max
motor
freq.
Frequency at which the device powers the motor.
x
x
Operating freq.2
f = XXX [Hz]
=
Max
motor
freq.
Frequency at which the device powers the motor.
x
Freq.min.control
fmin = XXX [Hz]
50
Minimum frequency below that the pump must try to
stop following the control ramp (Control ramp).
x
x
Stop delay
t = XX [s]
5
Delay with which the pump is attempted to be stopped
below the minimum control frequency (Freq.min.con-
trol ).
x
x
Control ramp
t = XX [s]
40
Time in which the device decreases the motor power
frequency from the minimum control frequency
(Freq.min.control ) to the minimum motor frequency
( Min motor freq.). If during this time the measured val-
ue falls below Set value - Delta control, the device re-
starts the motor. Otherwise the device will stop the mo-
tor completely following the control ramp (Control
ramp).
x
x
Delta start
p = XXX.X [bar]
0.5
This parameter communicates by how much the meas-
ured value must fall from the set value for the previously
stopped pump to be restarted.
x
x
Delta control
p = XXX.X [bar]
0.1
This parameter communicates by how much the meas-
ured value must fall in relation to the set value so that
the pump, during shutdown in control ramp, is restarted.
3
4
5
6
bar
1
2
sec
Hz
1: Min motor freq.; 2: Freq.min.control ; 3: Delta control;
4: Set value ; 5: Stop delay; 6: Control ramp
x
x
Delta stop
p = XX.X [bar]
0.5
This parameter represents the increment of the meas-
ured value with respect to the set value that must be ex-
ceeded in order for there to be a forced shutdown of the
pump according to the stop ramp.
x
x
Ki
XXX
Integral coefficient used in constant value control.
x
x
Ki
XXX
Proportional coefficient used in constant value control.
x
x
COMBO
ON/OFF
OFF
Enabling of the COMBO function for the combined oper-
ation of several pumps in parallel. Read the dedicated
chapter.
x
x
PSDrive
38