MST-5C USER’S GUIDE
MST-5C
Section C-29
High Alarm Relative Temperature
AL HI
This parameter is used to establish the relative temperature at which a high
temperature alarm condition will occur. When
Average Temperature
is
above the
Main Set Point
+
High Alarm Relative Temperature
, a high
temperature alarm condition will occur. This limit may be affected by the
Outside Probe
if that probe is used and the
Relative Outside
Temperature Alarm
is set to a value other than
OFF
. This parameter is
adjusted in 0.1° increments from 0.5°F to 40.0°F (0.3°C to 22.2°C).
Critical High Alarm
Crit
This parameter is used to establish the temperature set point at which a
high temperature alarm condition will occur regardless of the
Outside
Probe
reading. When the
Average Temperature
is above this parameter, a
high temperature alarm condition will occur. Setting this parameter to
OFF
will deactivate the critical high alarm check. This parameter is
adjusted in 0.1° increments from -40.0°F to 119.9°F (-40.0°C to 48.8°C),
OFF
.
Average / Probes (POS 12)
Average Temperature
This parameter displays the actual average temperature of all activated
inside probes. The average is made from the inside temperature probes
whose DIP SWITCH is set to the ON position (see DIP Switches and Slide
Switches Table page 38). The
Average Temperature
is displayed to the
nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C).
Probe 1
P
:
1
This parameter displays the actual probe 1 temperature. The
Probe 1
temperature is displayed to the nearest 0.1° from -58.0°F to 140.0°F
(-50.0°C to 60.0°C).
Probe 2
P
:
2
This parameter displays the actual probe 2 temperature. This parameter will
appear only if DIPSW2 is set to the ON position (see DIP Switches and
Slide Switches Table page 38). The
Probe 2
temperature is displayed to
the nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C).
Probe 3
P
:
3
This parameter displays the actual probe 3 temperature. This parameter will
appear only if DIPSW3 is set to the ON position (see DIP Switches and
Slide Switches Table page 38). The
Probe 3
temperature is displayed to
the nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C).
www.monitrol.com
Summary of Contents for MST-5C
Page 3: ...MST 5C WIRING DIAGRAM MST 5C Section A 3 WIRING DIAGRAM MST 5C SECTION A www monitrol com ...
Page 6: ...MST 5C INSTALLATION Section B 6 MST 5C INSTALLATION MST 5C SECTION B www monitrol com ...
Page 19: ...MST 5C USER S GUIDE MST 5C Section C 19 USER S GUIDE MST 5C SECTION C www monitrol com ...
Page 43: ...MST 5C INDEX WARRANTY MST 5C Section D 43 INDEX WARRANTY MST 5C SECTION D www monitrol com ...
Page 47: ...www monitrol com ...
Page 48: ...MST 5C_EN VER 1 3 November 20 2012 www monitrol com ...