MST-5C USER’S GUIDE
Section C-30
MST-5C
Probe 4
P
:
4
This parameter displays the actual probe 4 temperature. This parameter will
appear only if DIPSW4 is set to the ON position and DIPSW5 is set to the
OFF position (see DIP Switches and Slide Switches Table page 38). The
Probe 4
temperature is displayed to the nearest 0.1° from -58.0°F to
140.0°F (-50.0°C to 60.0°C).
Outside Probe
P
:
Out
This parameter displays the actual outside probe temperature. This
parameter will appear only if DIPSW4 and DIPSW5 are both set to the ON
position (see DIP Switches and Slide Switches Table page 38). This
reading may increase the high temperature alarm threshold. The
Outside
Probe
temperature is displayed to the nearest 0.1° from -58.0°F to 140.0°F
(-50.0°C to 60.0°C).
Humidity Probe
P
:
rH
This parameter displays the actual humidity probe readout. This parameter
will appear only if DIPSW8 is set to the ON position (see DIP Switches and
Slide Switches Table page 38). This parameter may display
ERR
if the
humidity probe is defective or unplugged. Otherwise, the
Humidity Probe
reading is displayed to the nearest 1RH% from 0RH% to 100RH%.
System Mode Settings
(POS 1)
MSP Curve
CSETP
This parameter is used to activate or deactivate the growth curve function of
the
Main Set Point
. If this parameter is set to
ON
and the
Growth Day
is not
OFF
, the
Main Set Point
will follow its day and value points and
will no longer be adjustable. See the Additional information on parameters
section for more information on the growth curve. If this parameter is set to
OFF
, the
Main Set Point
will not be affected by its growth curve.
(POS 5)
Logic Out 4
OUT 4
This parameter is used to select the mode in which output 4 will operate. If
this parameter is set to
COOL
, output 4 will activate when the
Average
Temperature
is high. If this parameter is set to
HEAT
, output 4 will
activate when the average temperature of the probes selected in
Probe {1-
4}
Heater 2
is low.
www.monitrol.com
Summary of Contents for MST-5C
Page 3: ...MST 5C WIRING DIAGRAM MST 5C Section A 3 WIRING DIAGRAM MST 5C SECTION A www monitrol com ...
Page 6: ...MST 5C INSTALLATION Section B 6 MST 5C INSTALLATION MST 5C SECTION B www monitrol com ...
Page 19: ...MST 5C USER S GUIDE MST 5C Section C 19 USER S GUIDE MST 5C SECTION C www monitrol com ...
Page 43: ...MST 5C INDEX WARRANTY MST 5C Section D 43 INDEX WARRANTY MST 5C SECTION D www monitrol com ...
Page 47: ...www monitrol com ...
Page 48: ...MST 5C_EN VER 1 3 November 20 2012 www monitrol com ...