2.5.1 Single Temperature Probe
Install a single temperature probe in an area that best
reflects the overall temperature of the room. Connect the
two leads and the shield of the temperature probe to the
control panel terminals labelled “Probe” as indicated in
Figure 4.
2.5.2 Averaging (optional)
Four temperature probes are required if temperature
averaging is desired in larger rooms. Place the probes in
appropriate locations to best average room temperature.
Refer to Figure 5.
2.5.3 Humidity Probe (optional)
Install one humidity probe in an area that best reflects the
overall room humidity. Connect the humidity probe to the
control panel terminals labeled “Probe” as indicated in
Figure 4.
2.6 ALARM
The ECS-2M provides a normally open and normally
closed dry contact for alarming low or high temperature
conditions. In addition, this same contact can be used to
signal a power failure. This contact may be connected to
an alarm system, or directly to a siren and/or auto-dialer.
Make normally open or normally closed connections as
indicated in Figure 4
Use shielded cabling for probes . Connect the shields
to “SHLD” terminal. Failure to do so may result in
inaccurate readings!
Momentary power interruptions may trigger false
alarms! To avoid false alarming when the ECS-2M is
connected to an alarm system, install a time delay
relay between the ECS-2M and the alarm system.
CHAPTER 2 - INSTALLATION
www.monitrol.com
Summary of Contents for ECS-2M
Page 8: ...Page 8 ECS 2M www monitrol com ...
Page 19: ...Page 19 Fig 7 Recommended control backup CHAPTER 2 INSTALLATION www monitrol com ...
Page 21: ...Page 21 CHAPTER 3 USER S GUIDE www monitrol com ...
Page 41: ...Page 41 APPENDIX www monitrol com ...
Page 42: ...Page 42 ECS 2M www monitrol com ...
Page 48: ...MAV ECS 2M Ver 1 0 June 5 2001 www monitrol com ...