Page 24
ECS 2M
The Fan 1 modulation band setting establishes the
temperature at which Fan 1 reaches maximum speed.
The value is a temperature
difference
from the main
set point.
The Fan 1 modulation band is adjusted in 0.5 degree
increments from a minimum setting of 2.0°F (1.0°C) to
a maximum setting of 18.0°F (10.0°C).
Adjusting the Fan 1 modulation band:
•
rotate the Selector dial to position (2),
•
rotate the adjustment dial counterclockwise to
decrease the temperature setting, clockwise to
increase it.
The Fan 1 modulation band setting is displayed on the
ECS.
Example: A main set point temperature
of 70°F along with a Fan 1 band setting of
5°F is set. When the temperature of the
room reaches 75°F, Fan 1 operates at its
maximum speed.
FAN 1 MOD. BAND
2
www.monitrol.com