PRIMARY FUNCTIONS
The main set point establishes the target
temperature in the building. This value is used
as the reference point for other settings. The
main set point temperature is adjusted in 0.5
degree increments from a minimum setting of
13.5°F (-9.5°C) to a maximum setting of 105.0°
F (41.0°C).
Adjusting the main set point temperature:
•
rotate the Selector dial to position (1),
•
rotate the Adjustor dial counterclockwise to
decrease the temperature setting,
clockwise to increase it.
The main set point temperature is displayed on
the ECS.
Note: The reduction per day feature
(primary function 9) must be (OFF) to
adjust the main set point.
CHAPTER 3 - USER’S GUIDE
MAIN SET POINT
1