Page 37
Minimum ramping is the lowest value that the ramping
function can adjust the main set point to. This is a
security feature.
The minimum ramping setting is adjusted in 0.5 degree
increments from a minimum setting of 13.5°F (-9.5°C)
to a maximum setting of 105.0°F (41.0°C).
Adjusting the minimum ramping setting:
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and forth to
enter secondary function mode,
•
rotate the Selector dial to position (9),
•
rotate the Adjustor dial counterclockwise to decrease
the minimum ramping setting, clockwise to increase
it.
The minimum ramping setting is displayed on the ECS.
NOTE: When the main set point
temperature reaches the minimum
ramping limit, the reduction per day
setting (primar y function 9)
automatically shuts off.
CHAPTER 3 - USER’S GUIDE
MINIMUM RAMPING
9