2.4.1.2 - 230 VAC
Assure that the line voltage selector switch is set to
230 VAC.
Connect the power cable to terminals 5 and 6
on the main (bottom) board, connect the ground wire to
terminal 7 on the main board.
2.4.2 - Fan 1 (terminals 3 and 4)
Stage 1 of the ECS-2M controls the operation of the
primary fan. Connect the two leads from Fan 1 to
terminals 3 and 4 on the main (bottom) board.
2.4.3 - Fan 2/Heater (terminals 1 and 2)
Stage 2 of the ECS-2M provides a dry contact closure
which controls the operation of a second fixed speed fan
or a heater. This contact closure is voltage rated to 230
VAC. The current rating of the dry contact is 10 Amps
(resistive) for a heater and 6 Amps (inductive) for a fan.
Set the software settings DIP switch behind of the control
panel faceplate to ON for a fan or OFF for a heater.
Connect the heater or Fan 2 to terminals 1 and 2 on the
main (bottom) board.
2.5 TEMPERATURE / HUMIDITY PROBES
Temperature and humidity probes use a “Class 2” low
voltage circuit. These cables can extend up to a distance
of 500 feet (150 meters). Single probe temperature and
humidity connections are illustrated in Figure 4, while
temperature probe averaging connections are illustrated in
Figure 5.
www.monitrol.com
Summary of Contents for ECS-2M
Page 8: ...Page 8 ECS 2M www monitrol com ...
Page 19: ...Page 19 Fig 7 Recommended control backup CHAPTER 2 INSTALLATION www monitrol com ...
Page 21: ...Page 21 CHAPTER 3 USER S GUIDE www monitrol com ...
Page 41: ...Page 41 APPENDIX www monitrol com ...
Page 42: ...Page 42 ECS 2M www monitrol com ...
Page 48: ...MAV ECS 2M Ver 1 0 June 5 2001 www monitrol com ...