Technical description
5 Control functions
5.8 Auto-reclose function (79)
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
155
Measured and recorded values of AR function:
Parameter Value
Unit Description
Measured
or
recorded
values
Obj1
UNDEFINED;
OPEN;
CLOSE;
OPEN_REQUEST;
CLOSE_REQUEST;
READY;
NOT_READY;
INFO_NOT_AVAILABLE;
FAIL
-
Object 1
state
Status
INIT;
RECLAIM_TIME;
READY;
WAIT_CB_OPEN;
WAIT_CB_CLOSE;
DISCRIMINATION_TIME;
LOCKED;
FINAL_TRIP;
CB_FAIL;
INHIBIT
-
AR-function
state
Shot#
1…5
-
The
currently
running shot
ReclT
RECLAIMTIME;
STARTTIME;
DEADTIME;
DISCRIMINATIONTIME
-
The
currently
running time
(or last
executed)
SCntr
-
Total start
counter
Fail
-
The counter
for failed AR
shots
Shot1 *
-
Shot1 start
counter
Shot2 *
-
Shot2 start
counter
Shot3 *
-
Shot3 start
counter
Shot4 *
-
Shot4 start
counter
Shot5 *
-
Shot5 start
counter
*) There are 5 counters available for each one of the two AR signals.