Technical description
3 Supporting functions
3.2 Disturbance recorder
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
107
Disturbance recorder parameters
Parameter
Value
Unit
Description
Note
Mode
Saturated
Overflow
Behaviour in memory full
situation:
No more recordings are
accepted
The oldest recorder will be
overwritten
Set
SR
32/cycle
16/cycle
8/cycle
1/10ms
1/20ms
1/200ms
1/1s
1/5s
1/10s
1/15s
1/30s
1/1min
Sample rate
Waveform
Waveform
Waveform
One cycle value
*)
One cycle value
**)
Average
Average
Average
Average
Average
Average
Average
Set
Time
s
Recording length
Set
PreTrig
%
Amount of recording data
before the trig moment
Set
MaxLen
s
Maximum time setting.
This value depends on
sample rate, number and
type of the selected
channels and the
configured recording
length.
Status
Run
Trig
FULL
Status of recording
Not active
Waiting a triggering
Recording
Memory is full in saturated
mode
ManTrig
Trig
Manual triggering
Set
ReadyRec
n/m
n = Available recordings
m = maximum number of
recordings
The value of 'm' depends on
sample rate, number and
type of the selected
channels and the
configured recording
length.