2.2 Local panel operations
2 Local panel user interface
Operation and configuration
16
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Second menu of U>> 59 stage
Figure 2.2.2-2 Second menu(next on the right) of U> 59 stage
This is the main setting menu. The content is:
Stage setting group 1
These are the group 1 setting values. The other setting
group can be seen by pressing push buttons ENTER and
then RIGHT or LEFT. Setting groups are explained in
chapter 2.2.3.
ILmax 0V
The maximum of three measured voltages is at the moment
0V. This is the value the stage is supervising.
Status –
Status of the stage. This is just a copy of the status value in
the first menu.
U>> 13000 V
The pick-up limit is 13000 V in primary value.
U>> 130%Un
The pick-up limit is 1,3 times the rated voltage. This value
can be edited if the operating level is at least “Operator”.
Operating levels are explained in chapter 2.2.5.
t>> 0.10s
The total operation delay is set to 100 ms. This value can be
edited if the operating level is at least “Operator”.