4.4 Symmetric components
4 Measurement functions
Technical description
104
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
Example 2, two phase injection with adjustable phase angle
U
N
= 100 V
Voltage measurement mode is "2LL+Uo+LLy/LNy".
Injection:
U
A
= U
12
= 100 V
0°
U
B
= U
23
= 100/
3 V
150° = 57.7 V
150°
30
2
.
19
30
5
.
38
30
3
/
1
30
3
/
2
3
100
30
3
/
1
0
1
90
3
/
1
0
1
3
100
150
3
/
100
0
100
1
1
3
1
2
2
1
a
a
U
U
U
1
= 38.5 %
U
2
= 19.2 %
U
2
/U
1
= 50 %
Figure 4.4-2 shows a geometric solution. The input values have been scaled
with
3/100 to make the calculation easier.