2.5 Volts/hertz over-excitation
protection Uf> (24)
2 Protection functions
Technical description
54
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
The setting unit is per unit (PU).
RATED
RATED
f
U
PU
1
, where
U
RATED
is the nominal voltage of the protected device and f
RATED
is the basic network frequency.
Parameters of the volts/hertz over-excitation stage U
f
> (24)
Parameter
Value
Unit
Description
Note
Status
-
Blocked
Start
Trip
Current status of the stage
F
F
SCntr
Cumulative start counter
C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SGrpDI
-
DIx
VIx
LEDx
VOx
Digital signal to select the
active setting group
None
Digital input
Virtual input
LED indicator signal
Virtual output
Set
Force
Off
On
Force flag for status forcing for
test purposes. This is a
common flag for all stages and
output relays, too.
Automatically reset by a 5-
minute timeout.
Set
Umax
V
The supervised value. Max. of
U12, U23 and U31
f
Hz
The supervised frequency
value
U/f
%
Calculated Umax/f
Uf>
%
Pick-up setting
Set
t>
s
Definite operation time
Set
For details of setting ranges see chapter 9.3.
Set = An editable parameter (password needed)
C = Can be cleared to zero
F = Editable when force flag is on
Recorded values of the latest eight faults
There are detailed information available of the eight latest
faults: Time stamp, fault voltage, fault frequency, elapsed delay
and setting group.