Technical description
6 Communication
6.1 Communication ports
VM265.EN011
VAMP 24h support phone +358 (0)20 753 3264
139
6.1.3.
Extension port X4
This is a non-isolated RS-485 port for external I/O devices. The
port is located in the same rear panel D9S connector X4 as the
local port, but pins (7, 8, 5) are used instead of the standard
RS-232 pins (2, 3, 5) used by the local port. See Figure 6.1-1.
Parameters
Parameter Value
Unit Description
Note
Protocol
None
SPA-bus
ProfibusDP
ModbusSla
ModbusTCPs
IEC-103
ExternalIO
DNP3
Protocol selection for the
extension port.
Command line interface
for VAMPSET
SPA-bus (slave)
Profibus DB (slave)
Modbus RTU slave
Modbus TCP slave
IEC-60870-5-103 (slave)
Modbus RTU master for
external I/O-modules
DNP 3.0
Set
Msg#
0 ... 2
32
1
Message counter since the
device has restarted or
since last clearing
Clr
Errors
0 ... 2
16
1
Protocol errors since the
device has restarted or
since last clearing
Clr
Tout
0 ... 2
16
1
Timeout errors since the
device has restarted or
since last clearing
Clr
speed/DPS
Default =
38400/8N1 for
VAMPSET
Display of actual
communication
parameters.
speed = bit/s
D = number of data bits
P = parity: none, even, odd
S = number of stop bits
1)
Set = An editable parameter (password needed)
Clr = Clearing to zero is possible
1) The communication parameters are set in the protocol specific menus. For
the local port command line interface the parameters are set in
configuration menu.