![VAMP 265 Operation And Configuration Instructions Download Page 140](http://html1.mh-extra.com/html/vamp/265/265_operation-and-configuration-instructions_3326045140.webp)
6.1 Communication ports
6 Communication
Technical description
140
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
6.1.4.
Ethernet port
IEC61850 and Modbus TCP uses Ethernet communication.
Also VAMPSET, SPA-bus and DNP 3.0 communication can be
directed via TCP/IP.
Parameters
Parameter
Value
Unit Description
Set
Protoc
None
ModbusTCPs
IEC 61850
Ethernet/IP
Protocol selection for the
extension port.
Command line interface
for VAMPSET
Modbus TCP slave
IEC-61850 protocol
Ethernet/IP protocol
Set
Port
nnn
Ip port for protocol,
default 102
Set
IpAddr
n.n.n.n
Internet protocol
address (set with
VAMPSET)
Set
NetMsk
n.n.n.n
Net mask (set with
VAMPSET)
Set
Gatew
default = 0.0.0.0
Gateway IP address (set
with VAMPSET)
Set
NTPSvr
n.n.n.n
Network time protocol
server (set with
VAMPSET)
0.0.0.0 = no SNTP
Set
VS Port
nn
IP port for Vampset
Set
KeepAlive
nn
TCP keepalive interval
Set
MAC
nnnnnnnnnnnn
MAC address
Msg#
nnn
Message counter
Errors
nnn
Error counter
Tout
nnn
Timeout counter
Set = An editable parameter (password needed)
Summary of Contents for 265
Page 2: ...VM265 EN011...
Page 219: ...VM265 EN011...