Technical description
7 Applications
7.4 Current Transformer Selection
VM265.EN011
VAMP 24h support phone +358 (0)20 753 3264
161
Marking:
Accuracy limit factor is written after the accuracy class.
E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20.
The actual accuracy limit factor k
A
depends on the actual
burden.
Equation 7.4.1-3.
A
i
N
i
ALF
A
S
S
S
S
k
k
k
ALF
= Accuracy limit factor at rated current and rated burden
S
i
= Internal secondary burden. (Winding resistance R
CT
S
N
= Rated burden
S
A
= Actual burden including wiring and the load.
Figure 7.4.1-2 This figure of Equation 7.4.1-3 shows that it is essential to
know the winding resistance R
CT
of the CT if the load is much less than the
nominal. A 10 VA 5P10 CT with 25% load gives actual ALF values from
15..30 when the winding resistance varies from 0.5
to 0.05
.