INSTALLER’S GUIDE
Page
10
4.12
If the appliance is to
be fitted against a wall with
combustible cladding, the
cladding must be removed
from the area shown in
figure 2
4.13
Combustible side
projections up to 75mm
forward of the fixing plane
of the fire are to be a
minimum of 125mm from
the fireplace opening (See
figure 3)
4.14.1
Combustible side
projections greater than
75mm forward of the fixing
plane of the fire are to be a minimum of 178mm from the fireplace opening (See
figure 3).
4.14.2
Non-combustible side projections to be 75mm from the fireplace
opening (See figure 3)
Figure 2. Removal of Combustible cladding