Figure 45 Wind Direction Voltage Output with WS425 Cable and Adapter Cable
5.15 Limitations for Output Signals
You can specify the minimum and maximum values for analog output with the configuration
parameters. The output is fixed to the specified values, and the unit depends on the selected
analog output mode.
Example
To limit the output 1 in voltage mode to a range of 0.1 … 5 V, set the analog output
minimum value to 0.1 and the analog output maximum value to 5. Type the following
commands:
S aout1minv,0.1 S aout1maxv,5
5.16 Missing Readings and Error
Indication
If WMT700 is unable to measure the wind, it indicates a missing reading in the output. The
most common reasons for measurement problems are foreign objects (such as ice, birds, or
other foreign object) on the line of measurement or sound reflections from nearby objects
(such as wind tunnel walls).
WMT700 User Guide
M211095EN-H
132