![Vaisala WINDCAP WMT700 Series User Manual Download Page 151](http://html.mh-extra.com/html/vaisala/windcap-wmt700-series/windcap-wmt700-series_user-manual_849074151.webp)
VAISALA WMT700 200
5.24.1.2 Wx — Start Measurement
This command starts wind measurement based on averaging time and fetches the data
automatically when the measurement has finished. You must specify the averaging time in
the command.
The averaging time supplied in the command (
x
) sets the averaging time for WMT700.
When you change the averaging time, it applies to the next new wind value.
Wx
x
Time for averaging wind speed and wind direction. The range is from 1 to 9
WMT700 responds to the
Wx
command with a 19-character fixed-length data message.
Character
Description
1
┐
02H (<STX>, start of transmission)
2
W
3
Averaging in seconds
4
Status: P = Pass F = Fail
5
Wind direction (most significant digit)
6
Wind direction (middle digit)
7
Wind direction (least significant digit)
8
Wind speed (most significant digit)
9
Wind speed (next digit)
10
Wind speed (next digit)
11
Wind speed (least significant digit)
12
. (dot character)
13
Wind speed (tenth digit)
14
Wind speed unit:
M = Miles per hour
K = Knots
L = Kilometers per hour
T = Meters per second
Chapter 5 – Operation
149
Summary of Contents for WINDCAP WMT700 Series
Page 1: ...M211095EN H User Guide Vaisala WINDCAP Ultrasonic Wind Sensor Series WMT700 ...
Page 32: ...WMT700 User Guide M211095EN H 30 ...
Page 100: ...WMT700 User Guide M211095EN H 98 ...
Page 168: ...4 Remove the verifier WMT700 User Guide M211095EN H 166 ...
Page 174: ...WMT700 User Guide M211095EN H 172 ...
Page 182: ...WMT700 User Guide M211095EN H 180 ...
Page 194: ...WMT700 User Guide M211095EN H 192 ...
Page 198: ...WMT700 User Guide M211095EN H 196 ...
Page 201: ...Appendix G Certificate Appendix G Certificate 199 ...
Page 202: ...WMT700 User Guide M211095EN H 200 ...
Page 208: ...WMT700 User Guide M211095EN H 206 ...
Page 209: ......
Page 210: ...www vaisala com ...