Maintenance Manual________________________________________________________________
68 __________________________________________________________________ M210886EN-G
Monitoring CDU Status
You can monitor the status of the CDU(s) from the
System Status
panel.
-
Green heartbeat icon: System is operating normally.
-
Red heartbeat icon: The heartbeat signal has not been received from
the CDU because a persistent CDU failure has been detected. For
example, the CDU has been turned off or it has crashed, or there is a
failure in the connection to the CDU.
-
In duplicated systems: One of the CDUs is active and the other is in
Hot standby mode in normal operation. For information on CDU
mode and switch-over, see
You can continue troubleshooting the problem by doing the following:
-
Click the numbers in the columns for the CDU, for example, in the
Missing processes
column in the
System Status
panel. See section
Monitoring ROA Processes and Applications on page 71
.
-
Check the event messages in the
Events
with Messages Related to CDU(s) on page 82
.
-
Click the faulty CDU in the optional
Overview
panel to display the
CDU details in the Device details panel. See section
the Overview Panel (Optional) on page 74
You may need to change the active CDU, see section
.
For instructions on troubleshooting a missing CDU or network problem,
see Diagnostics application section
MISSING ROA SERVER OR NETWORK PROBLEM DETECTED BY
SERVER X on page 83