background image

22

Split Type User Manual

9  Troubleshooting

The table below describes a series of problems with 
their possible causes and solutions, see Table 9.1.
If these solutions do not solve the problem contact your 
usual installer or call your nearest SAT Vaillant service.

SYMPTOMS

POSSIBLE CAUSES

POSSIBLE SOLUTION

The system does not restart immediately

When unit is stopped, it won't restart until 3 
minutes have elapsed to protect the system

Wait 3 minutes before starting the unit again

When the electric plug is pulled out and 
inserted again, the protection circuit will 
work for thee minutes to ptotect the air 
condioner unit

Wait 3 minutes after inserting the plug and 
before starting the unit again

The system does not work at all (the 
ventilation does not start)

The power plug is not inserted

Insert the plug and start the unit by 
positioning the selector to "I" (start)

Power supply cut

Reconnect the power supply

The fuse has blown

Replace the fuse. Only use the right fuses 
for each model. Do not use wire or other 
material to replace the fuse. Fires could be 
caused

Insufficient cooling or heating

Doors and/or windows open

Close the doors and/or windows 

Heat source nearby (e.g. lots of people in the 
room)

If possible, remove the heat source

The thermostat is set to an excessively high 
temperature in cooling mode or excessively 
low in heating mode

Set the temperature properly

Obstacle in front of the air inlet or outlet

Remove the obstacle to allow the air to 
circulate properly

The ambient temperature has not reached 
the designated level

Wait for a few moments

Dirty or blocked air filter

Clean the air filter (the air filter should be 
cleaned every 15 days)

Is there any direct sunlight through the 
window during the cooling operation?

Use a curtain to protect the air conditioning 
unit

Noise is heard

During unit operation or when stopping the 
unit a gurgling noise may be heard. This 
noise is more audible the first 2-3 minutes of 
operation

This is normal in an air conditioning unit. 
The noise is caused by the refrigerant 
flowing in the system).

A cracking noise is heard during operation

This is normal in an air conditioning unit. 
The noise is caused by the casing expanding 
or shrinking due to the temperature changes

If the noise is loud and comes from the air 
flow during the unit operation, the air filters 
may be too dirty

Clean the air filters properly

Smells are generated

This is because the system circulates smells 
from the indoor surrounding (furniture, 
cigarettes)

This situation does not require any action

Mist or steam come are blown out from the 
unit

During COOL mode or DRY mode operation, 
the indoor unit may blow some mist. This is 
due to the sudden cooling of the indoor air.

This situation does not require any action

Table 9.1 Troubleshooting.

9 Troubleshooting

Summary of Contents for climaVAIR V 7-025 NW

Page 1: ...V 7 025 NW V 7 035 NW V 7 050 M2N V 7 060 M2N V 7 075 M3N V 7 085 M3N climaVAIR DE EN ES HR IT NL ...

Page 2: ...For the user User Manual Air Conditioner climaVAIR Split Type EN V 7 025 NW V 7 035 NW V 7 050 M2N V 7 060 M2N V 7 075 M3N V 7 085 M3N ...

Page 3: ...ical Airflow 14 7 6 2 Horizontal Airflow 15 7 7 Special Function Selection 15 7 7 1 Health Anion Operation HEALTH 15 7 7 2 Health Airflow Operation HEALTH FLOW 16 7 7 3 SLEEP Function 17 7 7 4 TIMER ON OFF Function CONNECTION DISCONNECTION USING TIMER 18 7 7 5 POWER SOFT Function 19 7 8 Emergency Operation and Operation Test 20 7 8 1 Emergency Operation 20 7 8 2 Operation Test 20 7 8 3 Cancellatio...

Page 4: ... and in the user manual Vaillant does not accept any responsability for damages that may arise from non observation of the following instructions Note The Installation of the unit has to be done by qualified people Do not install it yourself All electrical repairs should be also carried out by qualified electricians Note Please read this User Manual carefully before using the air conditioning Note...

Page 5: ...th the standard in force with regard to obtaining the CE Marking 5 Description of the Unit This unit is comprised of the following elements Outdoor unit Indoor unit Remote controller and holder Connections and channels Accessories Figure 5 1 shows the unit components Fig 5 1 Unit components Legend 1 Indoor Unit 2 Outdoor unit 3 Remote controller and holder 4 Connections and channels 5 Condensed wa...

Page 6: ...ting strange odours and maintaining a fresh atmosphere This filter s exposure to sunlight regenerates its anti odour capacity Anti bacterial filter Filter with an anti allergic and anti bacterial effect which keeps the atmosphere clean and healthy Anti dust filter Anti dust filter Remote controller Remote controller using infrareds Hot start function Start and stop with hot battery which avoids th...

Page 7: ...there is anything still showing on display just press the reset button Remove the batteries in case the air conditioning is out of use for a long period If there is anything still showing on display just press the reset button Warning Danger of the enviromental contamination by not disposing of the batteries properly When replacing the remote controller batteries leavethe old batteries in suitable...

Page 8: ...rface If the refrigerant spurts out and gets into your eyes it may result in serious eye injuries Do not interrupt the operation of the air conditioning unit by pulling the cord Danger of injury and physical damage Danger of fire and explosion Damaged air conditioners should not be put into operation In case of doubt consult your supplier The air conditioner must be properly grounded in accordance...

Page 9: ...WN button AIRFLOW DIRECTION UP DOWN 15 SWING LEFT RIGHT button AIRFLOW DIRECTION LEFT RIGHT 16 FRESH button 17 SET button SETTING 18 POWER SOFT button 19 RESET button 7 2 2 Display Indicators Fig 7 2 Overview of the indicators Legend 1 TIMER ON indicator 2 FAN SPEED indicator 3 LOCK indicator 4 SWING UP DOWN indicator AIRFLOW DIRECTION UP DOWN 5 SLEEP indicator NIGHTTIME FUNCTION 6 HEALTH indicato...

Page 10: ...nnection Disconnection of the Unit In order to connect the unit Press the ON button on the indoor unit or on the remote controller the unit will start to operate The liquid crystal display LCD will show the latest operating status of the unit except the HEALTH SLEEP POWER SOFT and TIMER ON OFF functions In order to disconnect the unit Press the OFF button on the indoor unit or on the remote contro...

Page 11: ...Press the TEMP buttons to select the temperature setting When pressing the TEMP buttons the temperature configuration will increase or decrease by 1ºC When keeping the TEMP buttons pressed the temperature configuration will increase or decrease quickly Press the FAN button to select the fan speed Each time the FAN button is pressed the fan speed will be modified as shown in Figure 7 7 Fig 7 7 Fan ...

Page 12: ...e or decrease by 1ºC When keeping the TEMP buttons pressed the temperature configuration will increase or decrease quickly Press the FAN button to select the fan speed Each time the FAN button is pressed the fan speed will be modified as shown in Figure 7 10 Fig 7 10 Fan speed The operation in cooling mode is started when the ambient temperature is greater than the configured one In dehumidifying ...

Page 13: ...ion mode Legend 1 MODE button 2 FAN mode indicator 3 FAN button In order to activate the fan mode FAN With the unit connected see section 7 4 Press the MODE button The different operation modes are displayed AUTO COOL DRY FAN HEAT Fig 7 13 Operation modes Select the fan operation mode FAN Press the FAN button to select the fan speed Each time the FAN button is pressed the fan speed will be modifie...

Page 14: ...elect the heating operation mode HEAT Press the TEMP buttons to select the temperature setting When pressing the TEMP buttons the temperature configuration will increase or decrease by 1ºC When keeping the TEMP buttons pressed the configured temperature will increase or decrease quickly Press the FAN button to select the fan speed Each time the FAN button is pressed the fan speed will be modified ...

Page 15: ...is recommendable to direct the grates vertically Note In cooling mode it is recommendable to direct the grates horizontally 7 6 1 Vertical Airflow Press the SWING UP DOWN button to direct the airflow upwards or downwards The vertical slat will be directed in accordance with the positions allowed for each operation mode On the remote controller or the control panel of the indoor unit the different ...

Page 16: ...th Anion Operation HEALTH The anion generator of the air conditioning unit has the following functions To generate anions to neutralise the quantity of cations and anions in the air To kill bacteria To accelerate the sedimentation of dust in the room to clean the room air UV light degerming function UV light emitted by the UV light device of the indoor unit catalitically activates the nano TiO2 on...

Page 17: ... and the airflow will circulate horizontally from the top inlet and outlet grates Press the HEALTH FLOW button again to direct vertically The vertical flow indicator will appear on the display The unit s top inlet and outlet grates will close and the airflow will circulate vertically from the bottom inlet and outlet grates Press the HEALTH FLOW button again to cancel the health airflow function Bo...

Page 18: ...d T1 Configured temperature to Start of the SLEEP function In HEAT mode The ambient temperature decreases 2ºC in relation to the configured one to ensure that the temperature does not rise excessively during the sleep hours During the first operating hour of the SLEEP function the ambient temperature will drop 2ºC below the configured temperature Once an hour has elapsed the temperature will drop ...

Page 19: ...he desired time When pressing the HOUR buttons the time configuration will increase or decrease by 1 minute If the HOUR buttons are kept pressed the time will increase or decrease rapidly The time can be set within an interval of 24 hours Press the SET button to confirm the time The ON or OFF indicators will stop flashing Time display the unit starts to operate or stops after x hours x minutes In ...

Page 20: ...atically in HI high for 15 minutes in order to put the configuration back to its original state To cancel the POWER function Press the POWER SOFT button twice The indicator will disappear To activate the SOFT function Press the POWER SOFT button Each time you press the button you will modify the display configuration see Figure 7 26 Stop the display in SOFT function In SOFT function the fan speed ...

Page 21: ...y operation operation test switch Legend 1 Emergency operation operation test switch Note When in emergency operation the dehumidifying mode is not available 7 8 2 Operation Test Only use this function to carry out operation tests when the temperature is less than 16ºC In order to activate Lift the front lid of the indoor unit Keep the emergency operation operation test switch pressed for more tha...

Page 22: ...om is heated In addition to the surfaces which delimit this area i e the walls doors windows ceiling and floor the adjacent rooms are also heated uncontrollably thermal energy is unintentionally lost It is therefore impossible to adequately heat the room and an unpleasant feeling of cold is felt the same occurs when leaving open doors which separate heated areas and unheated areas in a limited way...

Page 23: ...ture in cooling mode or excessively low in heating mode Set the temperature properly Obstacle in front of the air inlet or outlet Remove the obstacle to allow the air to circulate properly The ambient temperature has not reached the designated level Wait for a few moments Dirty or blocked air filter Clean the air filter the air filter should be cleaned every 15 days Is there any direct sunlight th...

Page 24: ...til it is released from the stopper and remove the filter downwards Clean the filter removing the dust or the dirt using a vacuum cleaner or cleaning them with cold water Ensure that the filters are dried completely dry in the shade before putting them back into the unit Attach the filter correctly and make sure it is completely fixed behind the stopper If the right and left filters are not proper...

Page 25: ...ary precautions are taken In order to do so follow the steps described in the installation manual in reverse order and use the necessary tools and protection resources Ensure that the disassembly is carried out by qualified technically competent individuals Warning Danger of environmental contamination when disposing of the unit To avoid this follow the instructions described in this section Warni...

Page 26: ......

Reviews: