INSTALLATION INSTRUCTIONS
vacon • 45
24-hour s358 (0)40 837 1150 • Email: [email protected]
7
Figure 7-9. Jumper selection for OPT-A1
!
NOTE
If you change the AI/AO signal content also remember to
change the corresponding board parameter in
menu M7
.
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
Jum per block X 1 :
AI1 m ode
AI1 mode: Voltage input; 0...10V
AI1 mode: Voltage input; 0...10V (differential)
AI1 mode: Voltage input; -10...10V
Jum per block X 2 :
AI2 m ode
AI2 mode: 0...20mA; Current input
AI2 mode: Voltage input; 0...10V
AI2 mode: Voltage input; 0...10V (differential)
AI2 mode: Voltage input; -10...10V
Jum per block X 3 :
CM A a nd CM B grounding
CMB connected to GN D
CMA connected to GN D
CMB isolated from GN D
CMA isolated from GN D
CMB and CMA
internally connected together,
isolated from GN D
= Factory default
Jum per block X 6 :
AO 1 m ode
AO1 mode: 0...20mA; Current output
AO1 mode: Voltage output; 0...10V
AI1 mode: 0...20mA; Current input