18 • vacon
technical data
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
4
Structure
Inom (output)
Motor cos
Idc (input)
FR6
4.5
0.81
4.7
5.5
0.82
5.9
7.5
0.83
8.1
10.0
0.84
10.9
13.5
0.85
14.9
18.0
0.85
19.9
22.0
0.86
24.6
27.0
0.86
30.2
34.0
0.86
38.1
FR7
41.0
0.87
46
52.0
0.87
59
FR8
62.0
0.87
70
80.0
0.88
92
100.0
0.88
115
Table 4- 5. DC currents of Vacon NX, supply voltage 640 - 1100Vdc
Structure
NXI_xxxx 5 / F
NXI_xxxx 6 / F
FR4 0003-0007
FR4 0009-0012
165
235
FR6
1000
500
FR7
1650
900
FR8
3300
1800
Table 5- 1. DC-link capacitance by structure.