82 • vacon
commissioning
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
8
6
Connect the inverter to DC supply.
7
Set the parameters of group 1 according to the requirements of your application (See
Vacon All in One Application Manual). At least the following parameters should be set:
motor nominal voltage
motor nominal frequency
motor nominal speed
motor nominal current
You will find the values needed for the parameters on the motor rating plate.
8
Perform run test without motor
Perform either Test A or Test B:
A Controls from the I/O terminals:
Turn the Start/Stop switch to ON position.
Change the frequency reference (potentiometer)
Check in the Monitoring menu M1 that the value of Output frequency changes according to
the change of frequency reference.
Turn the Start/Stop switch to OFF position.
B
Control from the control keypad:
Change the control from the I/O terminals to the keypad as advised in Chapter 7.3.3.1.
Press the START
button
on the keypad START.
Move over to the
M3 and Keypad Reference submenu (see Chapter
7.3.3.2 ) and change the frequency reference with the Browser buttons
+
-
.
Check in Monitoring menu M1 that the value of Output frequency changes according to the
change of frequency reference.
Press the STOP button on the keypad STOP.