Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4.1
Free space around the cabinet
Enough space must be left above, behind and in front of the cabinet to ensure sufficient cooling and
space for maintenance.
The amount of cooling air required is indicated in the table below. Also make sure that the
temperature of the cooling air does not exceed the maximum ambient temperature of the inverter.
Figure 6. Space to be left free above (left) and in front of (right) the cabinet
Type
Cooling air required [m
3
/h)
NXV0125
800
NXV0200
1000
NXV0400
2000
NXV0600
3000
NXV0800
4000
NXV1000
5000
NXV1200
6000
Table 4.
Required cooling air
200 mm
800 mm