Safety
vacon • 6
1
1.4
Insulation system
A distinction has to be made for the following three groups of terminals, according to the insu-
lation system of VACON
®
20 X:
•
Mains and motor connections (L1, L2, L3, U, V, W)
•
Relays (R01, R02)
(**)
•
Control terminals (I/Os, RS485, STO)
The Control terminals (I/Os, RS485, STO) are isolated from the Mains(the insulation is rein-
forced, according to IEC 61800-5-1) and
the GND terminals are referred to PE
.
This is important when you need to connect other circuits to the drive and test the complete
assembly. Should you have any doubts or questions, please contact your local Vacon distribu-
tor.
Figure 2. Insulation system(* only for MU3).
Please, consider carefully the insulation system depicted in Figure 2, before con-
necting any circuit to the unit.
The control unit of VACON
®
20 X fulfils the insulation requirements of the stan-
dard IEC 61800-5-1 regarding DVC A circuits and also the strongest insulation
requirements of IEC 60950-1 regarding SELV circuits.
(**)
The relays may be used also with DVC A circuits. This is possible only if both
relays are used for DVC A circuitry:
to mix Mains and DVC A is not allowed.