Technical data
vacon • 56
7
Communication
interface
Fieldbus
Standard: Serial communication (RS485/
Modbus);
Optional: CANopen; Profibus DP, DeviceNet
Status indicators
Drive status indicators (LED) on top side
(POWER, RUN, FAULT, READY)
Ambient conditions
Ambient operating tem-
perature
-10°C…+40°C
Extended temperature
range
up to 50°C with current derating(see chap-
ter 1.6)
Storage temperature
-40°C…+70°C
Relative humidity
0 to 100% R
H.
Good resistance to most
acids, alkalis and oils. Contact factory for
more details.
Pollution degree
PD2
Altitude
100% load capacity (no derating) up to
1,000m;
derating 1% / 100m at 1.000...3.000m
Degree of protection
IP66/Type 4X
Stationary vibration:
Sinusoidal
IEC 60068-2
MU2:
3 Hz
f
9Hz: 10mm
9 Hz
f
200Hz: 3g
MU3:
10 Hz
f
57Hz: 0.075mm
57 Hz
f
150Hz: 1g
Shock/Bump:
IEC 60068-2-29
MU2:
25g/6ms
3M7 (IEC 60721-3-3)
MU3:
--
Directives
EMC
2004/108/EC
Low Voltage
2006/95/EC
Standards
Immunity
EN61800-3 (2004), 1
st
and 2
nd
environment
Emissions
EN61800-3 (2004), Category C2 as standard.
The drive can be modified for category C4.
Safety
EN 61800-5-1
Approvals
Safety
TÜV - Mark
Declaration of
Conformity
USA, Canada
VACON
®
Compliance testing
EMC
TÜV - Tested
CE
EC Conformation Declaration
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]