84
13 - TROUBLE SHOOTING
Troubleshooting Chart 7
Check all wires including blower
valve are connected and tight
NO
YES
Replace Blower
Assembly
Connect all
wires and
assure secure
fit
Clear Vent
Obstruction
E34
- Fan Fault
Check venting for
obstruction (both inlet and
exhaust)
NO
YES
Troubleshooting Chart 8
Check BL connection on control
board terminal strip. Is this
function being utilized?
NO
YES
Secure wire
connections
Install jumper
securely in
place
Repair/Replace
External Accessory
Item As Required
E39
- Shutdown Input In Locked Out Mode
Are the wire connections
secure?
NO
YES
Is factory installed jumper
securly in place?
NO
YES
Check external
accessories are
correct
NO
YES
Check external
accessories are
correct
NO
YES
Replace Control
Board
Change Installation
Parameters As
Required
P/N 240011654, Rev. C [06/08/2017]