61
Parameters Settings - Continued
9 - START UP PROCEDURE
P47
Modulate back when dT >
this parameter
41 to 140ºF
5 to 60ºC
140º/60ºC
P48
DHW stabilization time
10 to 100 seconds
30
P49
Display units
0 = Metric
1 = Imperial
1
P50
Factor for average flow
temperature calculation
1 to 255 seconds
1
P51
Flue gas temperature
0 = PVC 65°C / 149°F
1 = CPVC 90°C / 194°F
2 = PP/SS 110°C / 230°F
1
P52
Air pressure sensor
0: Off
1: On
0
P53
DHW time out mode
0: None
1: Absolute
1
P54
DHW time out
10 to 180 minutes
150
P55
CH prior time
10 to 180 minutes
120
P56
RPM min antiwind
10 to 30 (*100rpm)
25
Parameter
Description
Adjustment Range
Factory Setting
UCS-240
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: Propane (gas E)
* Note: There are sea level values: please see Parameter Settings For High Altitude (section 2.2)
P/N 240011654, Rev. C [06/08/2017]