54
Important
I
1.
n a reset from lockout condition, all electrical meter readings at the gas control valve (24 vac) must be taken within the
trial for ignition period.
If any component does not function properly, make sure it is correctly installed and wired before replacing it.
2.
Static electricity discharge can damage the integrated boiler control (IBC). Touch metal surface to discharge static electricity
3.
before touching IBC.
The IBC cannot be repaired. If it malfunctions it must be replaced.
4.
Only trained, experienced service technicians should service the IBC systems. Following troubleshooting, check out the
5.
system following the sequence of operation section of this chapter for a normal light off sequence.
All controls are factory tested in the assembly process and a defective control is generally the least likely cause. If you suspect
6.
you have a defective control, read through the troubleshooting chart before you replace it.
It is extremely unlikely that the two consecutive controls are defective. If it seems to be happening, chances are that either
7.
there is nothing wrong with the contorl or it is being damaged by some other problem (an electrical short burning out a
transformer, for example).
Initial Service Checks
Before troubleshooting:
1.
Make sure that circuit breaker is on or fuse is ok at electrical panel.
A.
Make sure that service switch is on.
B.
Make sure that gas is on at the gas meter, at all appropriate manual shutoff valves and at the gas control valve.
C.
Make sure that the thermostat is calling for heat.
D.
Check that wire connectors at the integrated boiler control and at the originating control are securely plugged in or con-
E.
nected.
Check that hoses are securely connected and are not plugged in or damaged.
F.
Troubleshooting tools:
2.
Voltmeter to check 120 vac and 24 vac
A.
Continuity tester.
B.
Inclined manometer or pressure gauge with 0-2.0” Range (0.01” Scale) for measuring suction pressures at pressure switch.
C.
U-tube manometer or differential pressure gauge with 0-14” range (0.1” Scale) for measuring inlet and manifold gas pres-
D.
sures.
What is system status?
3.
Consult the chart on the following page.
A.
Figure #16
B.
shows the location on the boiler of the diagnostic indicator lamps.
Fire, explosion or shock hazard may cause property dam-
age, severe injury or death. Do not attempt to modify the
physical or electrical characteristics of this boiler in any
way.
WARNING
!
TROUBLESHOOTING
Summary of Contents for UB100
Page 15: ...15 Near Boiler Piping Figure 2 Single Zone Boiler Piping ...
Page 16: ...16 Figure 3 Multi zone Boiler Piping With Zone Valves Near Boiler Piping ...
Page 19: ...19 Figure 6 Diaphragm Type Expansion Tank Piping Near Boiler Piping ...
Page 20: ...20 Figure 7 Conventional closed type Expansion Tank Piping Near Boiler Piping ...
Page 27: ...27 Combustion Air and Vent Pipe Figure 11 Combustion Air and Vent Piping ...
Page 32: ...32 Electrical Wiring Figure 13 Field Wiring Connections ...
Page 53: ...53 DETAILED SEQUENCE OF OPERATION ...
Page 57: ...57 TROUBLESHOOTING CHART 2 TROUBLESHOOTING ...
Page 58: ...58 TROUBLESHOOTING CHART 3 TROUBLESHOOTING ...