46
The following steps and diagram indicate the location of the
connection points required to measure the manifold pressure.
The manifold pressure may be measured using a U-Tube Ma-
nometer or a Differential Pressure Gauge. The diagram shows
the connection of both measuring
devices. Only ONE DEVICE IS
REQUIRED to measure the mani-
fold pressure.
Remove the plug. Install the
appropriate barbed fitting and
connect the pressure side line
from the U-Tube Manometer or
Differential Pressure Gauge.
Refer to “CHECK OUT PROCE-
DURE AND ADJUSTMENTS”
in this manual when reading the
manifold pressure.
When measurement is completed,
disconnect the U-Tube Manome-
ter or Differential Pressure Gauge.
Be sure to reinstall the ⅛” plug,
using appropriate pipe thread sealant approved for use with
natural and liquefied Petroleum gases.
OFF
ON
INLET
OUTLET
GAS CONTROL KNOB
PRESSURE REGULATOR
ADJUSTMENT (UNDER CAP SCREW)
INLET
PRESSURE
TAP
VR8205
WIRING TERMINALS (2)
OUTLET
PRESSURE
TAP
NOTE: Regulator cover screw must be installed at all
times unless adjusting manifold pressure. Firing rate and
manifold pressure must only be measured with cover screw
firmly installed.
CHECK OUT PROCEDURE AND ADJUSTMENT
Figure 17 - Manifold Pressure Measurement Detail
Figure 18 - Gas Valve
Summary of Contents for UB100
Page 15: ...15 Near Boiler Piping Figure 2 Single Zone Boiler Piping ...
Page 16: ...16 Figure 3 Multi zone Boiler Piping With Zone Valves Near Boiler Piping ...
Page 19: ...19 Figure 6 Diaphragm Type Expansion Tank Piping Near Boiler Piping ...
Page 20: ...20 Figure 7 Conventional closed type Expansion Tank Piping Near Boiler Piping ...
Page 27: ...27 Combustion Air and Vent Pipe Figure 11 Combustion Air and Vent Piping ...
Page 32: ...32 Electrical Wiring Figure 13 Field Wiring Connections ...
Page 53: ...53 DETAILED SEQUENCE OF OPERATION ...
Page 57: ...57 TROUBLESHOOTING CHART 2 TROUBLESHOOTING ...
Page 58: ...58 TROUBLESHOOTING CHART 3 TROUBLESHOOTING ...