Classic P3 x/x - 240-840A
16
Direct power connection
Connection
Phase
L1
bolt X10:16
Phase
L2
bolt X10:15
Phase
L3
bolt X10:14
Note:
L1, L2, L3 - clockwise rotating
field
Protecting earth - PE connection
Unit P3
Type current
Power choke
KD-three-phase current
K-phase choke
Fuses A
super fast acting
installed
240
KD 5-250
3x250 A FF
360
K 170-400
3x315 A FF
480
KU 150-600
3x400 A FF
840
KU 150-800
3x500 A FF
Power connection with an auto-transformer
Transformer performance
1.1 x continuous motor power
Secondary voltage
0.9 x motor power
Transformer fuses
Slow acting
Observe the switch-on current!!!
Input fuses
F1, F2, F3
rf. to the table above
Attention:
If the secondary voltages produced by the transformer are inferior to 60%
the voltage watchdog has to be adapted. These modifications may only
be effected in the factory and thus, the voltages have to be indicated on
order.
Watchdog power connection
BTB inactive
dark LED
>>> missing phase
>>> wrong rotating field
Po
w
er
su
p
p
ly
Transformer guard
with filter