Classic P3 x/x - 240-840A
6
P3 400/450-x
Power connection
Auxiliary voltage connection
Output voltage
Cooling
360 ... 440V~
360 ... 440V~ or 200...250V~
max. +450V=
ventilation fan
P3 400/450-
240
360
Input current
A~
192
288
Output current
peak 5 s.
continuous
A=
A=
480
240
720
360
El. power
kW
108
162
Fuses
- input 3 pcs.
- field
ff
installed
installed
AFF
250
315
AF
10
10
Power chokes
Type
mH
1x KD5-250
0.12
3x K 170-400
0.08
Armature chokes
Armature choeks are necessary only for special
applications.
Type
mH
Ul180B250
2.2
Ul210C400
1.8
Dimensions w
x
h
x
d
mm
305x510x240
305x510x240
Wieght
kg
23
23
P3 500/550-x
Power connection
Auxiliary voltage
Output voltage connection
Cooling
450 ... 550V~
360 ... 440V~ or 200 ... 250V~
max. +550V=
ventilation fan
P3 500/550-
240
360
Input current
A~
192
288
Output current
- peak
- continuous
A=
A=
480
240
720
360
El. power
kW
132
198
Fuses
- input 3pcs.
- field
ff
installed
installed
AFF
250
315
AF
10
10
Power chokes
Type
mH
1x KD5-250
0.12
3x K 170-400
0.08
Armature chokes
Armature chokes are necessary only for special
applications.
Type
mH
Ul180B250
2.2
Ul210C400
1.8
Dimensions w
x
h
x
d
mm
305x510x240
305x510x240
Weight
kg
23
23
Te
ch
n
is
cc
a
l
d
a
ta