Installation, Operation and Maintenance Manual
VariCool EZ-Fit
9
Subject to change without notice.
Physical Data
Single Module
Nominal Tons
Blower Type
Filter Size
Evap. Coil
Compressor
R-410A
ECM iDDP DWDI
Qty
Size (in)
Rows FPI
Qty
Lbs/Ckt
15
•
•
•
4 / 2
15x20 / 20x20
4
14
2
7
20
•
•
•
6
18x25
4
14
2
10.8
25
•
•
•
6
18x25
4
14
2
11.8
30
•
•
6 / 3
24x20 / 20x20
5
14
2
15
35
•
•
2 / 5 / 2
20x20 / 20x24 / 24x24
5
14
2
20
40
•
•
3 / 6
14x24 / 25x25
6
14
2
24.1
45
•
•
3 / 6
14x24 / 25x25
6
14
2
27
Dual Module
Nominal Tons
Blower Type
Filter Size
Evap. Coil
Compressor
R-410A
ECM iDDP DWDI
Qty
Size (in)
Rows FPI
Qty
Lbs/Ckt
30
•
•
•
8 / 4
15x20 / 20x20
4
14
4
7
40
•
•
•
12
18x25
4
14
4
10.8
50
•
•
•
12
18x25
4
14
4
11.8
60
•
•
12 / 6
24x20 / 20x20
5
14
4
15
70
•
•
4 / 10 / 42
20x20 / 20x24 / 24x24
5
14
4
20
80
•
•
6 / 12
14x24 / 25x25
6
14
4
24.1
90
•
•
6 / 12
14x24 / 25x25
6
14
4
27
1. Standard Filters - 2” MERV 13, Optional Filters - 2” MERV 8 Pre- and 4” MERV 13 Final
2. Total Unit Working Fluid Pressure:
Coaxial Condenser (Std. A/C) - up to 250 psig
Brazed Plate Condenser (Std. WSHP) - up to 250 psig
Shell and Tube Condenser (Option) - up to 150 psig