Start-Up Procedures
(R-410a Systems)
Continued:
1�
If possible, record the fluid flow rate (GPM)
a�
Make sure the flow rate is within the proper limits:
i�
Minimum 25 GPM / Ton
ii�
Maximum 35 GPM / Ton
2�
Record the entering and leaving fluid temperatures
b�
Make sure the leaving fluid temperature is within the
proper limits:
i�
Minimum 60˚ F
ii�
Maximum 115˚ F
3�
Record the pressure drop of the water / fluid across the
unit
4�
Verify that all valves on each fluid circuit function
properly
5�
Record the suction line pressure and the suction line
temperature for each circuit near the compressor
6�
Using an appropriate pressure / temperature chart for
R-410a refrigerant, look up and record the saturation
temperature corresponding to the suction pressure
7�
Calculate and record the suction superheat for each
circuit by taking the difference between the suction
line temperature and the saturation temperature
corresponding to the suction pressure
8�
Record the liquid line pressure and the liquid line
temperature for each circuit near the condenser heat
exchanger outlet
9�
Using an appropriate pressure / temperature chart for
R-410a refrigerant, look up and record the saturation
temperature corresponding to the liquid line pressure
10�
Calculate and record the liquid sub-cooling for each
circuit by taking the difference between the liquid
line temperature and the saturation temperature
corresponding to the liquid line pressure
11�
Record the Amps for the evaporator blower motor and
each compressor If the system is single phase, use L1
and L2 only
a�
Make sure the pressures on each compressor circuit
are within the proper limits:
i�
290 – 550 Discharge
ii�
100 – 140 psig Suction
b�
Compressor Amperage is below the RLA Amps
listed on the unit data tag
i�
The maximum compressor operating current
(amps) at start up depends a lot on the system
loading The lower the load, the less the current
The higher the load, the higher the current
c�
The blower motor FLA value should never be
exceeded
i�
If the FLA value is exceeded, shut the unit off
and check the duct design, sheave turns open
or make sure there is no blockage / obstruction
in the duct or filters
12�
Document any additional information deemed
appropriate for the specific application or installation
13�
Shut the system down and remove all test instruments
and test sensors
14�
Leave the system in the operating mode as appropriate
for the customer and the application
Optional Heating Start Up:
15�
If the system has any optional heat, set the room
thermostat approximately 5
°
higher than the actual
room temperature Set the thermostat operating mode
to the HEAT position
16�
Dependent upon the heating source the heating valve
or switch / contactor should be activated
17�
After several minutes of operation, record the return air
temperature and the supply air temperature
18�
Based on the heating source, document the
appropriate temperatures, pressures, voltage or amp
values