Installation, Operation and Maintenance Manual
VariCool EZ-Fit
32
Subject to change without notice.
PROBLEM
POSSIBLE CAUSE
POSSIBLE SOLUTION
Suction
pressure
too low
1�
Flash gas in liquid line
2�
Obstructed expansion valve
3�
Loss of fluid in expansion valve bulb
4�
Clogged filter drier
5�
Lack of air flow
6�
Entering WB too low
7�
Evaporator blower running
backwards
1�
Check for refrigerant leak
2�
Repair leak, evacuate and recharge refrigerant
system
3�
Replace thermal expansion valve
4�
Replace filter drier
5�
Check filters and coil for any blockages
6�
Verify that blower is rotating in the proper direction
7�
Confirm that entering return air conditions fall within
acceptable range
8�
Reset low pressure safety switch if necessary
9�
Check phase of incoming power to unit Reverse any
two incoming power supply wires (except ground)
No cooling
1�
Controller not set properly
2�
Control wiring issue
3�
Controls in an alarm condition
4�
High or low pressure switch open
5�
Compressor thermal overload open
1�
Turn on and set controller for desired operation
2�
Check wiring connections against schematic
3�
Check all connections for tightness
4�
Check wire continuity
5�
Refer to controller troubleshooting
6�
Reset high or low pressure switch
7�
Compressor internal overload may require an
extended period of time (1 hour or more) to reset
Condensate
carry over
1�
Air flow too high
1�
Reduce air flow
Condensate
pump does
not run
1�
Check to see that power to the
pump is present
2�
Confirm that float is moves freely
3�
Confirm that dirt or algae is not
interfering with float action
1�
Locate and repair electric issue
2�
Clean float and sump
Condensate
pump runs
with no
discharge
1�
Tubing blocked or kinked
2�
Check valve blocked
3�
Impeller blocked
4�
Tubing elevation or run exceeds
head capability
1�
Inspect, clean or straighten as necessary
2�
Clean check valve
3�
Remove debris from pump impeller
4�
Verify tubing run is within pump head limitations