background image

035-19670-003 Rev. A (1004)

6

Unitary Products Group

Horizontal Installations With a Cooling Coil Cabinet

The furnace should be installed with coil cabinet part number specifi-
cally intended for Horizontal application. If a matching cooling coil is
used, it may be placed directly on the furnace outlet and sealed to pre-
vent leakage. Follow the coil instructions for installing the supply ple-
num. For details of the coil cabinet dimensions and installation
requirements, refer to the installation instructions supplied with the coil
cabinet 
The perforations in the wrapper flanges must be bent away from the
heat exchanger to create duct flanges so the air conditioning coil can be
properly seated on the furnace.
Attach the supply plenum to the air conditioning coil cabinet outlet duct
flanges through the use of S cleat material when a metal plenum is
used. The use of an approved flexible duct connector is recommended
on all installations. The connection to the furnace, air conditioning coil
cabinet and the supply plenum should be sealed to prevent air leakage.
The sheet metal should be crosshatched to eliminate any popping of
the sheet metal when the indoor fan is energized.
The minimum plenum height is 12” (30.5 cm). If the plenum is shorter
than 12” (30.5 cm) the turbulent air flow may cause the limit controls not
to operate as designed, or the limit controls may not operate at all. Also
the plastic drain pan in the under the air conditioning coil can overheat
and melt Refer to the installation instructions supplied with the air condi-
tioning coil for additional information.

Horizontal Installations Without a Cooling Coil Cabinet

When installing this appliance, the furnace must be installed so as to
create a closed duct system, the supply duct system must be con-
nected to the furnace outlet and the supply duct system must terminate
outside the space containing the furnace. When replacing an existing
furnace, if the existing plenum is not the same size as the new furnace
then the existing plenum must be removed and a new plenum installed
that is the proper size for the new furnace.
Attach the supply plenum to the furnace outlet duct flanges through the
use of S cleat material when a metal plenum is used. The use of an
approved flexible duct connector is recommended on all installations.
This connection should be sealed to prevent air leakage. The sheet
metal should be crosshatched to eliminate any popping of the sheet
metal when the indoor fan is energized. On all installations without a
coil, a removable access panel is recommended in the outlet duct such
that smoke or reflected light would be observable inside the casing to
indicate the presence of leaks in the heat exchanger. This access cover
shall be attached in such a manner as to prevent leaks.

Residential and Modular Home Horizontal Return Plenum 
Connections

The return duct system must be connected to the furnace inlet and the
return duct system must terminate outside the space containing the fur-
nace. When replacing an existing furnace, if the existing plenum is not
the same size as the new furnace then the existing plenum must be
removed and a new plenum installed that is the proper size for the new
furnace.
Attach the return plenum to the furnace inlet duct flanges. This is typi-
cally through the use of S cleat material when a metal plenum is used.
The use of an approved flexible duct connector is recommended on all
installations. The connection of the plenum to the furnace and all the
ducts connecting to the plenum must be sealed to prevent air leakage.
The sheet metal should be crosshatched to eliminate any popping of
the sheet metal when the indoor fan is energized.
The duct system is a very important part of the installation. If the duct
system is improperly sized the furnace will not operate properly. The
ducts attached to the furnace must be of sufficient size so that the fur-
nace operates at the specified external static pressure and within the air
temperature rise specified on the nameplate.
Attic installations must meet all minimum clearances to combustibles
and have floor support with required service accessibility.

IMPORTANT: 

If an external mounted filter rack is being used see the

instructions provided with that accessory for proper hole cut size.

ATTIC INSTALLATION

This appliance is design certified for line contact when the furnace is
installed in the horizontal left or right position. The line contact is only
permissible between lines are formed by the intersection of the top and
two sides of the furnace and the building joists, studs or framing. This
line may be in contact with combustible material.

SUSPENDED FURNACE / CRAWL SPACE 

INSTALLATION

The furnace can be hung from floor hoists or installed on suitable blocks
or pad. Blocks or pad installations shall provide adequate height to
ensure the unit will not be subject to water damage. Units may also be
suspended from rafters or floor joists using rods, pipe angle supports or
straps. Angle supports should be placed at the supply air end and near
the blower deck. Do not support at return air end of unit. All four sus-
pension points must be level to ensure quite furnace operation. When
suspending the furnace use a secure a platform constructed of plywood
or other building material secured to the floor joists. Refer top Figure 4
for typical crawl space installation.

SECTION III: FILTERS

FILTER INSTALLATION

All applications require the use of an internal or external filter. Filter(s)
and the filter retainer are not provided on all models Some models are
shipped with a high velocity filter that must be field installed. A field-sup-
plied internal or external filter and filter retainer hardware must be pro-
vided if the filter and the filter retainer are not shipped with the furnace.
Refer to Table 5 for the recommended filter size.

 FIGURE 3:  

Typical Attic Installation

When a furnace is installed in an attic or other insulated space,
keep all insulating materials at least 12 inches (30.5 cm) away from
furnace and burner combustion air openings.

 FIGURE 4:  

Typical Suspended Furnace / Crawl Space Installation

In any application where temperatures below freezing are possible,
see “BELOW FREEZING LOCATIONS”.

LINE CONTACT ONLY PERMISSIBLE
BETWEEN LINES FORMED BY THE
INTERSECTION OF FURNACE TOP
AND TWO SIDES AND BUILDING
JOISTS, STUDS OR FRAMING

SUPPLY AIR

VENT (MAINTAIN
REQUIRED CLEARANCES
TO COMBUSTIBLES

SHEET METAL IN 
FRONT OF FURNACE
COMBUSTIBLE AIR
OPENINGS IS
RECOMMENDED

SEDIMENT

TRAP

RETURN AIR

FILTER RACK 

MUST BE A 
MINIMUM 

DISTANCE

OF 18” (45.7 CM)

FROM THE 
FURNACE

30” MIN.

WORK AREA

12”

GAS PIPING

ANGLE IRON
BRACKET

1” MAX. BETWEEN
ROD & FURNACE

6” MIN. BETWEEN
ROD & FURNACE 

1” MAX. BETWEEN 
ROD & FURNACE

SUPPORT 
ROD

Summary of Contents for PT8

Page 1: ...ETY 1 DUCTWORK 3 FILTERS 6 GAS PIPING 7 ELECTRICAL POWER 9 VENT SYSTEM 11 SAFETY CONTROLS 16 START UP AND ADJUSTMENTS 16 WIRING DIAGRAM 24 LIST OF FIGURES Dimensions 5 Furnace Base Rectangular Blockof...

Page 2: ...ailure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combustible flooring sha...

Page 3: ...es shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage 1 A gas fired furnace for installation in a resident...

Page 4: ...mined by adding the Supply Duct Static Pressure reading to the Return Duct Static Pressure reading and adding the pressure drop across any applied a coil Tables 2 3 is to be used as a guide only to he...

Page 5: ...quired service accessibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size HORIZONTAL MODELS The supply air temp...

Page 6: ...duct flanges This is typi cally through the use of S cleat material when a metal plenum is used The use of an approved flexible duct connector is recommended on all installations The connection of th...

Page 7: ...pproved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figures 9 or 10 TABLE 5 Filter Sizes Cabinet Size Side in Side cm Bottom in...

Page 8: ...he gas valve when installing piping A wrench must be placed on the octa gon hub located on the gas inlet side of the valve Placing a wrench to the body of the gas valve will damage the valve causing i...

Page 9: ...OLARITY Ignition Control If the power supply polarity is reversed the control board will flash 9 times The furnace will not operate until the polarity is corrected LOW VOLTAGE CONTROL WIRING CONNECTIO...

Page 10: ...1 0 amp maximum during circulating blower opera tion HUMIDIFIER CONNECTION Two 1 4 0 64 cm spade terminals EAC and NEUTRAL for humidifier connections are located on the control board The terminals pr...

Page 11: ...codes and standards listed in these instructions Approved Modular Homes must be vented with an approved roof jack and may not be common vented with other appliances VENTING Category I venting consists...

Page 12: ...etails provided by the manufacturer of the power vent VENT PIPING ASSEMBLY The final assembly procedure for the vent piping is as follows 1 Cut piping to the proper length beginning at the furnace 2 D...

Page 13: ...ent sagging The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every 4 ft 1 22 m FAN ASSISTED COMBUSTION SYSTEM An appliance equipped with an...

Page 14: ...r a grille or screen shall have no dimen sion smaller than 0 25 6 4 mm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automa...

Page 15: ...NACE 1 An opening may be used in lieu of a duct to provide to provide the outside air supply to an appliance unless otherwise permitted by the authority having jurisdiction The opening shall be locate...

Page 16: ...RBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monxide poisoning or dea...

Page 17: ...cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing coupling 1 1 8 0 3 cm adapter There is a accessory kit 1PK0602 available from Source 1 which has the following items 12 30 cm length x 1 8 0 3 cm diameter...

Page 18: ...ivided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 14 times 0 00283 m3 of gas measured at...

Page 19: ...low adjustment seal screw and tighten securely Cycle the valve several times to verify regulator setting 7 Remove manometer and replace the outlet pressure tap plug Low Outlet Pressure Adjustment 1 T...

Page 20: ...urnace control Intermittent Blower Heating On cooling heating thermostats with a fan switch when the fan switch is set in the auto position and the thermostat calls for heating a circuit is completed...

Page 21: ...ps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 2125 CFM 60 17 m3 min Airflow 0 60 2035 CFM 57 62 m3 min Subtract the airflow 0 50 w c 125 Pa from the airflow 0 60 w c...

Page 22: ...0 1150 41 6 41 1 40 8 40 5 39 4 38 5 37 1 36 0 34 5 32 6 Low 1260 1260 1260 1260 1250 1200 1150 1110 1070 1010 35 7 35 7 35 7 35 7 35 4 34 0 32 6 31 4 30 3 28 6 100 1200 B High 1700 1620 1560 1480 139...

Page 23: ...1430 1410 1370 1340 1280 1220 1140 1040 890 730 40 5 39 9 38 8 37 9 36 2 34 5 32 3 29 4 25 2 20 7 Medium Low 1140 1170 1150 1120 1080 1040 970 890 760 630 32 3 33 1 32 6 31 7 30 6 29 4 27 5 25 2 21 5...

Page 24: ...d in U S A 035 19670 003 Rev A 1004 Copyright by York International Corp 2004 All rights reserved Supersedes 035 19670 002 Rev A 0704 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION IX W...

Reviews: